Agenda 04/08/2008 Item #16E 1
Agenda Item No. 16E 1
April 8, 2008
Page 1 of 14
EXECUTIVE SUMMARY
Recommendation to approve change order No.2 to work order No. PBS-FT -3971-
07-16 with Professional Building Systems (PBS) for the Primary Data Center
project
OBJECTIVE: To increase the scope of worK under WorK Order PBS-FT-3971-07-16
with Professional Building Systems (PBS) for the Primary Data Center project, in
accordance with contract 06-3971, Annual Contract for General Contractor Services.
CONSIDERATIONS: On August 14, 2007, Agenda Item 16F1, the Board of County
Commissioners approved WorK Order PBS-FT-3971-07-16 with Professional Building
Systems (PBS) for a Primary Data Center project. Unanticipated changes to the fire
suppression system design require a change in the original scope of worK. In order to
complete construction, changes were made to the fire suppression system design and
added in Change Order No.2, which is attached and itemizes the changes required.
Total previous change orders to date totaled $14,245. Change Order NO.2 brings the
total change order amount to $20,028 which exceeds the original WorK Order amount,
$179,484.00 by 11.17 %.
FISCAL IMPACT: The fiscal impact of Change Order NO.2 is $5,762,70 and funding is
available in the Fire Suppression of Data Center project 500361 in the County Wide
Capital Projects fund (301).
GROWTH MANAGEMENT IMPACT: There is no growth management impact
associated with this Executive Summary.
RECOMMENDATION: That the Board of County Commissioners:
1. Approves Change Order NO.2 to PBS-FT-3971-07-16 with Professional Building
Systems
2. Authorizes the Chairman to execute the Change Order
Prepared by: E. Michael Berrios, IT Operations Manager, Information Technology
Department
Page 1 of 1
Agenda Item No. 16E1
April 8, 2008
Page 2 of 14
COLLIER COUNTY
BOARD OF COUNTY COMMISSIONERS
Item Number:
Item Summary:
16E1
Meeting Date:
Recommendation to approve change order No.2 to work order No. PBS-FT-3971-07-16 with
Professional Building Systems (PBS) for the Primary Data Center project ($5,762.70)
4/6/200890000 AM
Prepared By
Michael Berrios
Network Operations Manager
Date
Administrative Services
Information Technology
3/13/2008 1 :24:59 PM
Approved By
Barry Axelrod
Information Technology Director
Date
Administrative Services
Information Technology
3/12/20085:14 PM
A pproved By
Kelsey Ward
Contract Administration Manager
Date
Administrative Services
Purchasing
3/26/20084:08 PM
Approved By
Kelsey Ward
Contract Administration Manager
Date
Administrative Services
Purchasing
3/26/20084:08 PM
Approved By
Len Golden Price
Administrative Services Administrator
Date
Administrative Services
Administrative Services Admin.
3/27/20084:02 PM
Approved By
OMS Coordinator
Applications Analyst
Date
Administrative Services
Information Technology
3/28/20087:47 AM
Approved By
Susan Usher
Senior Management/Budget Analyst
Date
County Manager's Office
Office of Management & Budget
3/28/200811:11 AM
Approved By
Leo E. Ochs, Jr.
Deputy County Manager
Date
Board of County
Commissioners
County Manager's Office
3/29/20089:16 AM
file://C:\AgendaTest\Exoort\ 1 04-Aoril%208.%202008\16.%20CONSENT%20AGENDA \ 16... 4/2/2008
(i)
Agenda item No. 16E 1
April 8, 2008
Page 3 of 14
Facilities Manal!ement Deoartment
WORK DIRECTIVE CHANGE
PROJECT NAME: Primary Data Center
CHANGE #3
DATE OF ISSUANCE: 3/13/08
EFFECTIVE DATE: 3/13/08
OWNER: Collier County Board of Commissioners
PROJECT#: 500511
CONTRACTOR: PBS
ENGINEER: Victor Latavish A.LA
You are directed to proceed promptly with the following change(s):
Description: Additional Dry Fire Suppression for APC Cabinet
Purpose of Work Directive Change: Due of the configuration and the amount of cabinets proposed by IT,
The Fire Suppression system will need to be modified to cover all the racks and computer hardware,
Attachments: Change order request forms from contractor, memo from Design Professional.
If a claim is made that the above change(s) have affected Contract Price or Contract Times any claim for a
Change Order based thereon will involve one or more of the following methods of determining the effect of the
changes(s).
Method of determining change in Contract Price:
o Unit Prices
l8"Lump Sum
o Other:
Method of determining change in Contract Times:
~Contractor's records
o Engineer's record
o Other
By:
By:
----
Estimated increase (decrease) in Contract Price
$ 5,783.00
ACCEPTED:
ent
03113/08 8:27 AM
MRR-11-2008 12:12 From: VICTOR LATRVISH RIR 2356436192
.
-
To:2397933795 Agenda Itell'l.IlJ0416E1
April 8, 2008
Page 4 of 14
Victor J. latavish, AlA Architect
FAX MEMORANDUM
Date:
MilICh 11,2008
Collier County Facilities Management
Robert Fuentes, Project Manager
Victor J. Latavish, AlA ~
441 Building F Primary Data Center
Fire Suppression
To:
Attn:
From:
Project:
Re:
The contractor has proposed a change order to add clOllll agent fire suppression system
detection devices and a nozzle to provide required coverage within the hot air
containment aisle between the APe racks. We believe the work is necessary and should
be included a change order. Until then we recommend approval by Work Directive.
Please note the lid over the center aisle was not discussed during coordination with APC
and may also affect operation of the backup HV AC units. We will confirm if additional
changes are needed.
Feel free to call if you have any questions, or if additional information is needed.
cc: Steven Stafford, PE
Mtmber of the: Amttican In$titute of mtlitttu AR. 11942
+100 Corporate Square, Suite cOO, Naplef. Flodclt HI(l.+
Ttlephcne Z'9.6..,.t66S
'rclefacsirnik 2.J9,64,.6I'9:t
MRR-11-2008 12:12 From:UICTOR LATAUISH AlA
03/87/2888 16:21 2396434293
2355435192 To: 2397933795
PROF~SSIONAL BLDG SV
Agenda Ite!;'\, SO'! 16E 1
PA-~pr~p', 2008
'1>ag'8 5 of 14
Change Order ReqUest'
Detailed (With e",.kdown of FOCO.), Grouped by EaCl1
Number
ProJeG\. 27553
Tel: f.l'lO
pl'Ofl!!ssianal DuQding SyMtm'IS
Collier County p""'.ry Dolo CenlM
3301 e. Tambml irlil E.c!;l
Napls&, Fl M1 1~
Bulld;na 'F
Chango 0_' RequOS!: 005
Dote, 212512008
To:
V1CtOrl..atavi$~
VIctor J. Latavtsh, A.IA
"100 Corporate Square
Suite 100
NI"Ie,,- A 34104
Prom:
et.phl!;n .,I1g(~el'\
ProfQUiOMI Bulldina SySI8l'l'\a
4395 CO~Of'llle SQUillre
I'\ilClp!ft, FI 34104
Description
Aclditbnal Dry Fire SlJpprassioo for 'S:nclosed APC SeNGl' Cabinet
Category
$IIlM
P2nding
Reference
R@qUi"'d!ly
3/1. 012008
Days Req
30
AIIlt Rill
5,783
Notes
PCO No Cate
Reference
AlI.t ~rop Cays Req Category
Re"",,"
D..........:...t1Vt,
N....tBlIt
oo~
:lI3I1OO8
5,7&3
so
enlnge Order Field Ccnc:J1tion
Additional Dry Fire $up;)ft5$lon for APe Cebit'let
1, A4d one ;dditional nozzte to tne lntetior (If the enclosed ""'0 server
cabinet. lnoree$t tank =~Q te accommodate I1lghl!/' flow cak8.
2. Add two smOKe detectorr. to t~ interior of the ttnetosed A~ alDrver
cubinet
a. Revise pllns and 9ubo'lit CI ~~iDn with CQlller County.
Item No
00'
002
003
Item DMCripdOft
Ory Fin! Sprinkler
Projed; ~:lnagement
Buikle", ~Qe
Amt Prop Reference
5.057
200
52tl
Approved By:
Signature
Name
Cate
Printed on: 315r.moe
prOlog e, Projects
Page 1
Prolog M.,.gC,.
-
MRR-11-2008 12:12 ~rom:VICTDR LATAVISH AlA
63/67/2888 16:21 2396434293
2366436192
To: 2397933795
PRlJFE55IONAL BLDG 51'
Agenda Itell'.t30416E1
PA~~pril 8, 2008
-r-agl!16 of 14
..,_..
. - - - ' - - -.'"
FlagshilfFire;-Inc~----
"A SDecialtY 511:;:- e.yion and ~n Company"
_ ::. . ...~.. I'lt: MS,,732,0181
PH' P41-713.1UV us,~ ii:w.,UIlftG, .lll.u""" fl._
Monday, February 25, ZOOfl
Mr. ate". Jonlall
PrcfeS8ional Building Systems Inc
4395 COrporate 6qua'"
Nllples, f'L 34104
REI COllier COUnty Prl_ry Data center
ReqUl!$t fftr Chanae #1
Dear Sieve:
Based on Rob Hanington's meeting with you and till! engineer last week, it has
been determined ttm additional deledIon and suppression naeds to be added to the
~m to protect the APe Hot isle containment system design,
This unit beCOmea an obstl\lction to the oP'i'ratiOn of the fire suppression syatem
based on its length ll!1d width, Although \I1e Clean agent is a 3 dimensional
suppressant, I cannot gUBl'llntee the dean agent wilt SUppr8SS the fire inside the cabinet
with!" the 7 to 10 QEOCOndlO as ~quired by lI1e manufacturers c1esign criteria without an
addItional nOzzle.
,TrIa delection is ~190 oD&trucled and subsequently could cau&e a delay in lt1e
de1ection process: ThiS IS Why we are requiring the addition of two smoke detecto
Ins.de the APe unit. Our request ror eIIllnge is as follows: rs
AIIlI_ far Chanae #11 For the total ft"
FIre, Inc, intends 10 ' n ,l",ce of 55.057.00 Flagship
smoke detecto~ at ~ I=:~~;~:l~~ ~np~ eert,ify the addition of 2
Increase \he tank size to ace ad uOII, add 1 nozzle and
"ddllional nozzle, We also intenr;n: ~~ ~ flow calculatlons for the
10 the, county for approval. The s m mmit ,the ~re protection draWings
and IFlStaNed in accordange :::: NF~dlflcatiOna shall be designed
recommendations. This WOrk wnr not beg" PI "anel the manufadurer'a
our at'fice, ,n una a letter or PO Is sent 10
Once this change l1as been acce
unit and the actual heigm Of tIl~ I~ ':1 need a cad drawing of the APe
agent reQuil'l!d. un calculate tIlII Quantity Of clean
.....
MRR-11-2008 12:12 From:VICTOR LRTRVISH RIR 2366436192 To: 2397933795
e31e7/2008 15:21 2396434293 PROFE55[G,AL SLDG SY
Agenda 11273 tJl9'l16E1
Aprll'8, 2008
PA~gej' of 14
Mr. steve Jordan
ProfellSional Building Systems Inc
Monday, February 25, 2008
Page #: 3
Payment terms: liS stated in original proposal
E_ptIons : as stated in original proposal
Qualifications: as stated in original proposal
Your immediate attention to thilo issue would be appreciated. Thank you for your
continued Interest in Flagship Fire, Inc. Please feet free to call should you require any
aClCliUOnal infonnation,
Sincerely,
Flagship Fire, Inc.
~!c~a~I./j., ~:~
AJ.J,.J~d:l. ...,w.--.<:=u'
11 r~lal t. Dlnt;2OIaQUS01:3B:ll..oS'OO.
Michael Angstadt
President
/.(f ad'ir~~~Y1~~/
CONTRACTIWORK ORDER MODIFICATION
CHECKLIST FORM
. lAgei!3~..16E1
72 '-Apm-t( 2008
Page 8 of 14
PROJECT NAME: Primary Data Center PROJECT #:50051-1 PROJECT MANAGER: Robert Fuentes
BID/RFP #: 06.3971 MOD #: l.
PO#: 45-00083403
WORK ORDER II: PBS-FT-3971-07-16
DEPARTMENT: Infonnation Technoloales
CONTRACTOR/FIRM NAME: Professional Buildina SYStems
Original Contract Amount:
$ 179,484.00
(Starting Point)
$ 179,484,00
(Last Total Amount Approved by the BCe)
Current BCC Approved Amount:
Current Contract Amount
$ 193.729.00
(including All Changes Prior To This Modification)
Change Amount:
Revised ConlracllWork Order Amount:
$
$
",783.09 S-'7/:';(. ;70
i]9/Q 70
199.
(Including This Change Order)
Cumulative Dollar Value of Changes to
This ConlracllWork Order:
$
o0'11()
20,lI2&:9&-
Date of Last BCC Approval 8/14/07
Agenda Item # 16F 1
5"
11.1'%
Percentage of the change over/under current contract amount
Formula: (Revised Amount I Last BCe approved amount}-1
CURRENT COMPLETION DATE (S): ORIGINAL: January 3. 2008
CURRENT: ADril 30, 2008
Describe the change(s): The additional Fire Suppression for the Server Racks and HVAC Linear systems are
required by Fire Code due to the configuration of the equipment.
Specify the reasons for the change(s) r 1. Planned or Elective r 2. Unforeseen Conditions n 3. Quantity
Adjustments - 4. Correction of Errors (Plans, Specifications or Scope of Workl. 5. Value Added
r 6. Schedule Adjustments Note: One or more may be checked, depending on the nature of the change(s).
Identify all negative impacts to the project if this change order were not processed: These changes are
necessary due to Fire Code \/Iolatlons In the space and to accommodate new servers been purchase by the IT
Dept .
Thit,cnange was requested by: -Icontractor/Consultant rI Owner IIIiI Using Department C CDES
rDesign Professional rlRegulatory Agency (Specify) ENFD
r Other (Specify)
REVIEWED BY:
r Ves
II" No
Date:
.3 pi
~/;l 'I/o%'
Date:
Revised 11.19.2007
;'.genda item No. 16E 1
'April 3, 2008
Page 9 of 14
CHANGE ORDER
CHANGE ORDER NO.2
CONTRACT NO.06-3971
BCC Date: 8/1412007
Agenda Item: 16F 1
TO: Stephen Jordan
Professional Buildina Svstems
4395 Coroorate Sauare
Naples, FI 34104
DATE: March 17 2008
PROJECT NAME: Primary Data Center
PROJECT NO: 500511
Under our AGREEMENT dated August 21, 2007.
You hereby are authorized and directed to make the following change(s) in accordance with
terms and conditions of the Agreement:
1) Install additional Dry Fire Suppression system for the APC Sever and HVAC Cabinets, J /J/J
. ~ - ~rl~d.14
FOR THE (Additive) (Deductive) Sum of: Five Thousand Seven Hundred 9~R d re,
55,78300 S'160<,70 Q/Y\t5Z 4~>1tr ae~ &J
3': 1/- tl f
Present Agreement Amount
$ 179.484.00
$ 14.245,00
$5783.90 S7b,l. '70
$ 199,tJ.i6tliJ
Original Agreement Amount
Sum of Previous Changes
This Change Order (Add) (Dadwd)
The time for completion shall remain the same. Your acceptance of this Change Order shall
constitute a modification to our Agreement and will be performed subject to all the same terms and
cond~ions as contained in our Agreement indicated above, as fully as if the same were repeated in
this acceptance. The adjustment, if any, to the Agreement shall constitute a full and final settlement
of any and all claims of the Contractor arising out of or related to the change set forth herein, including
claims for impact and delay costs.
AccePted:~, 2008
CONTRACTOR:
Professional Building Systems
B:
Robert Fuentes, proj ct Manager
(i)
Agenda Item No. 16E1
April 8, 2008
Page 10 of 14
Facilities Manaeement Department
WORK DIRECTIVE CHANGE
PROJECT NAME: Primary Data Center
DATE OF ISSUANCE: 3/13/08
OWNER: CoUier County Board of Commissioners
CONTRACTOR: PBS
CHANGE # 3
EFFECTIVE DATE: 3/13/08
PROJECT#: 500511
ENGINEER: Victor Latavish AJ.A .
You are directed to proceed promptly witb tbe following cbange(s):
Description: Additional Dry Fire Suppression for APC Cabinet.
Purpose of Work Directive Change: Due of the configuration and the amount of cabinets proposed by IT,
The Fire Suppression system will need to be modified to cover all the racks and computer hardware.
Attachments: Change order request forms from contractor, memo from Design Professional.
If a claim is made that the above change( s) have affected Contract Price or Contracc Times any claim for a
Change Order based thereon will involve one or more of the following methods of determining the effect of the
changes(s).
Method of determining change in Contract Price:
o Unit Prices
~LwnpSwn
o Other:
Estimated increase (decrease) in Contract Price
SS,i'iJ.ll&- .5;76J--1IJ JJ,-v>> tj~Or
ACCEPTIO>. ~ 3-)
By:
,
~
UI
Method of determining change in Contract Times:
~Contractor's records
o Engineer's record
o Other
By:
---
ent
03113/08 8:27 AM
1111
.
~-11-20B8 12:12 From:VICTOR LATAVISH AlA 2366436192 To: 239?933795
BlfB7I2BB9 16'21 2a964~429~ f'I<U''"''''t~ IUJG SY
Agenda ilem No. 16E 1
April 8, 2008
Page 11 of 14
P.2'4
PAGE 61
Change Order Request I
oetaftod tovIth ~"Iulown of PCOI). Graulle<ll>)' EaCII
Number
COIl... Cggnly """'"'" _ Ce...
m1 E. T_ T<tO Eat
...,....F\.M1~2
ItJttclInaF
___ Z75U
T.I: PP;,
f". . r .... ~lnlJ a,.ttwnl
c_o_......-.. ....
"..., 212&12001
To:
VQair L..-tlftf\
VIdDr 01. 1.aarMh. .o\IA
C1QD corporate Squtrt:
Bu" 1DV
N....L FI 31104
Prom:
OWpMn"ord,,,
~1.utldinQ 9yttllll"/W,
a95 COrponltlt ScaJMW
....... FI 3410&
D..cripdon
.*Il:kimnal Ofy FiN 9-.JpP.R1I*tWEMll... APC s.rv- c..binet
CotegOfy
.......
Pand'"
--
",""U1rvdllY
3J1t)1Z;OI)t
Days _
""
-Reel
"k~.70
HolM
!'CO 110 llato
ReI_
..... ....p g_ J\oq Cootogory
-
e
"'11_..
N_b..
DOC "'!fiOO8
ACIdllJONll Dry 1'1/8 $uppTeMlon fOr....~ cabIroet
5.783 30 Q'lIT'lg!Ordel" Fttlll Coramon
1. Add ono &ctdllionlll ntm:.te 10 tht 1nWIortlft"- wncfOted NI>O ..Nltr
~bInet. Inoru.. t.-.Il: ~ teI:1toommoc"a I'IIglw I'tCW Gaka.
2. Add Iwo amolt;. .h!ct~ to \he In'-rig.r rIf IhI ..etoMd A-c HF'llW
tlIiIblMl,
a. ArIiM p&.ftI. Mlf tubcTlit I ,..mion wIl;h Cgl_r COr.6\l)",
_Ne
00'
002
0C3
......~0fI
0'1'''' S_
ptOjo<<Mo.......'_.
BuitW& F..
AmtPl'Op~ce
4.057
200
__ 50." 7IJ
S1t:,;(.70 ./.1-. .,J
~"J If -ott
J
Ap...- By:
SigMtul"8
-
lleIt
--
Prlnhd 0"; 3I'5J2QD8 PT'OIOg es P~C:ta
~... ,
Agenda 11em I~o. 16E 1
April 8, 2008
Page 12 of 14
1'JR-11-2008 12: 12 F.om:VICTI:R LRTAVISH RIR 2366436192
To: 23'37933795
P.l....4
. Victor J. Latavish, AlA Architect
FAX MEMORANDUM
Dale: March 11, 2008
To: Collier County Facilities Management
Attn: Robert Fuentes, Proj""t Manager
From: Victor J. Latavish, AJA lIl1
Project: 441 Building F Primary Data Center
Re: Fire Suppression
The contractor has proposed a cbaDge order 10 add clc:en agent fire suppression s)'!!em.
detection devices and a nozzle to provide required coverage within tho hot oil
containment aisle betWeen the APe racks. We believe me wodc is necessary and should
be included a change order. Until then we m:ommend approval by Work Directive.
Pl..... note the lid over the center Risle WIlS not discussed during coordination with APC
and may also affect opendionoftbe backup HVAC units. We will confirm ifaddltioual
changes are needed.
Feci fiw to c:all if you haY<: aoy questions, or if additionol inil>llIIlItion is needed.
c:c: Steven Stafford, PE
/"""
MaaIItt of die Amftian hDtilule of ~ AR. 1194$
+lOOC6fPO"lUSquarc.SWtc1oo.NapIcI.F1otid.a '410+
TdcpMor; :',IljI.6+J.l66S
icler.nuN. :.".",.61':
Agenda 11em N",-1-6E-1-
April 8. 2008
Page 13 of 14
MAR-11-20BB 12:12 F.om=VICTI:R LATRVISH ~I~
B3/B7/2eBB 16:21 ~39G.3.29]
To: 2397933795
PRCFESSIIJNIlL llUlG SV
2366436192
P.3"4
PAtE 82
FlagshrpFire;-IIiC~----.
_.. Sa ~ SU~ -....., and ~~:: eonaDllllY" l'XI-.-...A
"" t&1-1%J." _ - 17"': 111. lid &,.' d
MondaY. Feb1II8IY 25, :zooe
.- --.---..
Mr. _ JClld..
1', ~le "lIonal BuIlding SlsI'lms loe
~! CorpOllIllt Sque....
H.......I'L 34104
0: CClIIMr (;DUnty l'rln*'I DIlI8 01'"
II . .r....a.......#l
Delr SlIIVe:
Baeed on Rob NontT1JtO"'l rnd1lo 19 .nth you and llle engineer last _k, It hlilll
beeR de\ermil'*f !hlIt llddItiOnIIl duteallan and MJPIlI8SSion nMda to be lidded to the
..,-em to pruta<t "'e p.pe Hot isle CD,llloi,.,..nl sys1llm deSIlln.
Thla unit IHo<lOmes an obStruction to lII8 operatIOn ~ tIIa file suppreuion system
blIsed on \l>> Ioongth gnd w\dttI. AlthOUgh tha Clean agent is a 3 dlmell18ionlll
soppresaant, I ClInnot g.."'_ lII8 c1e1lll agent will supp..... the fire inaide the Cllbinel
"'""In lII8 7 to 10 8eCOnCls ... J1OClU\r1Kl by "'" manuf8ClUI'Bn> design crl1leIIa wt\hOUt IIIl
IICId1tIonol nOZZle.
The deb!etlan i. alac Clb&Iruclled end subsequentty could causa a oetay In !he
deIeclion procell. illlS il why _ _ requlll~ 1Ile addition of two smoke delelllOnt
...Ide "'" APe unIl. Our request lllr ehanga Ia Il$ follllw!!:
_ - liar Che.- .1. For \he total .........
PI...., IDC. inbonda tQ ledesIgn 1nsIa1l- of ~..lI5,.1IO Flagolllp
~moke detlIao.. allhll eefllnS .::~~ ~ ~~ ~It. the allditiOn 01 2
Increase the tank &izu lD acalm un add 1 noZ2lA and
additional nozzle. Wa allo fnlend:=': tow calculaUons for the
III the COlInly fOr approval. T'hol syatem ~~~-!_OflllnlvltngS
and Installed in aecordllnae wl1t1 ,,-".......... snerl be deelgnad
recom,"","d8llon.. 'ThIs WOrk Wftl not ~PA and the mamA'1lClurers
our olIIce. ......n until " letter or PO Is eenllO
Once thIS Change nas llee
unit end lhe _ he' n ao:eplad I will nead " cad draw;
agent requinod. IglII Of IIle unn to calculate "'a qU~:- ~
I
Myeflud Ilelll I\lU. I oc. I
April 8. 2008
Page 14 of 1
MAR-ll-20BB 12:12 F.om:VICTOR LRTRVISH RIR 2366436192 To: 2397933795
~~/U7/2B8B 16:21 2396434293 PROFESSIONAL BUDG SV
P.4'4
PMIO: B3
Mr. steve Jord8n
P, ...b.4ona1 BuIIdi~ SY$lIIma Inc
Monday, FebnIlIIy 25, 2008
..... IJI .1
....#1...4 W1nI: as sta1ed in original pl'OpCl881
....pa_ I .. aIIIled In original prop<l8IiII
QUllIin...1lI,,1E 8. stat8cI in original pl'OpOSllf
Y_ im",..cbl8 ..-n to 'da iseue would ~ ap~.ed. Thank you for your
continuecl ~ In l'1agshlp I"lre, IMe. Please feel free to 08n should you Illquire any
adlliliOna. hftl~.
Sincerely,
Flagship Fire, Inc:.
~!~ha~l/i.',"~,
A~~' .....,_n_
Mll;i1Hl Angatldl
PrMiclent