Backup Documents 07/26/2011 Item #17B
COLLIER COUNTY FLORIDA
REQUEST FOR LEGAL ADVERTISING OF PUBLIC HEARINGS
78
To: Clerk to the Board: Please place the following as a:
xxx Normal legal Advertisement
(Display Adv., location, etc.)
o Other:
**********************************************************************************************************
Originating Dept/ Div: Public Utilities Planning and Proiect Management Department Person: Nathan Beals Date: 07/08/2011
Petition No. (If none, give brief description): None
Petitioner: (Name & Address): N/A
Name & Address of any person(s) to be notified by Clerk's Office: (If more space is needed, attach separate sheet) See Above
Hearing before
BCC
BZA
Other
Requested Hearing date: (Based on advertisement appearing 10 + days before hearing.) July 26, 2011 (NOTICE TO RUN NO
LATER THAN THURSDAY, July 14, 2011)
Newspaper(s) to be used: (Complete only if important):
XXX Naples Daily News
o Other
xxx Legally Required
Proposed Text: (Include legal description & common location & Size: A RESOLUTION OF THE BOARD OF COUNTY
COMMISSIONERS OF COLLIER COUNTY, FLORIDA AS EX-OFFICIO THE GOVERNING BOARD OF THE W ATER-
SEWER DISTRICT APPROVING AMENDMENTS TO THE COLLIER COUNTY WATER-SEWER DISTRICT'S
UTILITIES STANDARDS MANUAL, WHICH IS AN INTEGRAL PART OF COLLIER COUNTY ORDINANCE NO. 2004-
31, KNOWN AS THE COLLIER COUNTY UTILITIES STANDARDS AND PROCEDURES ORDINANCE, WHICH IS
CODIFIED IN CHAPTER 134, ARTICLE III OF THE CODE OF LAWS AND ORDINANCES; PROVIDING FOR A
DELAYED EFFECTIVE DATE OF AUGUST 1, 2011 FOR THE MANUAL
Companion petition( s), if any & proposed hearing date: N/ A
Does Petition Fee include advertising cost? 0 Yes XXX No If Yes, what accoun~ ~hDSq~iSing costs:
P.O. #
Reviewed by:
Division Administrator or Designee Date
List Attachments:
Proposed Ordinance
DISTRIBUTION INSTRUCTIONS
A. For hearings before BCC or BZA: Initiating person to complete one copy and obtain Division Head approval before
submitting to County Manager. Note: If legal document is involved, be sure that any necessary legal review, or request
for same, is submitted to County Attorney before submitting to County Manager. The Manager's office will distribute
copies:
o County Manager agenda file: to
Clerk's Office
o Requesting Division
D Original
B. Other hearings: Initiating Division head to approve and submit original to Clerk's Office, retaining a copy for file.
***********************************************************************************************************
FOR CLERK'S OFFICE USE 9f2(.' '" . J, I ,-1
Date Received: -=2ltJ Date of Public hearing: ~ Date Advertised: ~a.-l
17 B .,\ ""'1
Ann P. Jennejohn
From:
Sent:
To:
Subject:
Attachments:
Neetvirginia [VirginiaNeet@colliergov.net]
Friday, July 08, 2011 1 :59 PM
Ann P. Jennejohn
FW: Advertising Request
Advertising Request - 7-8-11.docx
Ann:
Will there be a problem if this doesn't get to you today???
Dinny
From: BealsNathan
Sent: Friday, July 08, 2011 1:55 PM
To: NeetVirginia
Cc: WhiteJennifer
Subject: RE: Advertising Request
Thank you, attached is the updated request. I've gotten it signed by my Administrator but am waiting on a PO that I'm
working on pushing through today. The latest will be Monday. I've talked with Barbetta, she says that we'll probably be
able to get it in the Naples News on the 14th (even on Monday). Let me know if you see any issues.
Thank you,
Nathan Beals, PMP
Project Manager
Collier County Public Utilities Planning and Project Management Department
239-252-2583 (Office)
239-877-8284 (Cell)
239-252-6460 (Fax)
3339 East Tamiami Trail, Suite 303
Naples, Florida 34112
From: NeetVirginia
Sent: Friday, July 08, 2011 10:21 AM
To: BealsNathan
Cc: WhiteJennifer
Subject: Advertising Request
Nathan:
See attached as discussed. Please call if you have any questions.
Dinny
--------------------------------------------------------------------------------------
--------------------------------------------------------------------------------------
Virginia A. Neet, Legal Assistant
Office of the Collier County Attorney
Telephone (239) 252-8066 - Fax (239) 252-6600
1
178
. ~ ~
Ann P. Jennejohn
From:
Sent:
To:
Cc:
Subject:
NeetVirginia [VirginiaNeet@colliergov.net]
Friday, July 08, 2011 2:17 PM
Ann P. Jennejohn
White, Jennifer; Williams, Steven
RE: Advertising Request
Ann:
The attorney and I just confirmed the Resolution title is correct. Please proceed. We also have the attorney's OK for this
to run 11 days in advance of the hearing.
Thank you again!!
Dinny
From: Ann P. Jennejohn [mailto:AnnJenneiohn@colliercierk.coml
Sent: Friday, July 08, 2011 2: 11 PM
To: NeetVirginia
Subject: RE: Advertising Request
If this is the title that's to be printed, we should be o.k.
At least I could get it ready to shoot over to the paper
Let me know what else I can do and if I should go ahead and
get the ad formatted with the proposed text that's on the ad sheet @
Thanks!
Ann
From: NeetVirginia rmailto:VirginiaNeet@collierqov.netl
Sent: Friday, July 08, 2011 1:59 PM
To: Ann P. Jennejohn
Subject: FW: Advertising Request
Ann:
Will there be a problem if this doesn't get to you today???
Dinny
From: BealsNathan
Sent: Friday, July 08, 2011 1:55 PM
To: Neetvirginia
Cc: WhiteJennifer
Subject: RE: Advertising Request
Thank you, attached is the updated request. I've gotten it signed by my Administrator but am waiting on a PO that I'm
working on pushing through today. The latest will be Monday. I've talked with Barbetta, she says that we'll probably be
able to get it in the Naples News on the 14th (even on Monday). Let me know if you see any issues.
1
17 8 ~,~: ~tat
#059405
July 8,2011
Attn: Legals
Naples News Media Group
1100 lmmokalee Road
Naples, FL 34110
Re: Amending the Collier County Water-Sewer District's
Utilities Standards Manual
Dear Legals:
Please advertise the above referenced notice on Thursday, July 14, 2011, and
kindly send the Affidavit of Publication, in duplicate, together with charges
involved, to this office.
Thank you.
Sincerely,
Ann J ennej ohn,
Deputy Clerk
P.O. #4500111144
17 8 1_.
Ann P. Jennejohn
From:
Sent:
To:
Subject:
Attachments:
Ann P. Jennejohn
Friday, July 08, 2011 4:38 PM
Naples Daily News Legals
Amending Water-Sewer Utilities Standards Manual
Amending WSD Utilities Standards Manual (7-26-11 ).doc; Amending WSD Utilities Standards
Manual.doc
Hi again,
Please advertise the attached on Thursday, July 14, 2011.
Thank you!
Ann Jennejohn, Deputy Clerk
Clerk of the Circuit Court
Clerk of the Value Adjustment Board
Collier County Minutes & Records Dept.
239-252-8406
239-252-8408 (Fax)
1
178
\ f?~.
r"'~,
NOTICE OF INTENT TO CONSIDER RESOLUTION
Notice is hereby given that the Board of County Commissioners of
Collier County will hold a public hearing Tuesday, July 26, 2011
in the Boardroom, 3rd Floor, Administration Building, Collier
County Government Center, 3299 Tamiami Trail East, Naples,
Florida. The meeting will begin at 9:00 A.M. The title of the
proposed Resolution is as follows:
A RESOLUTION OF THE BOARD OF COUNTY COMMISSIONERS OF COLLIER
COUNTY, FLORIDA AS EX-OFFICIO THE GOVERNING BOARD OF THE
WATER-SEWER DISTRICT APPROVING AMENDMENTS TO THE COLLIER
COUNTY WATER-SEWER DISTRICT'S UTILITIES STANDARDS MANUAL,
WHICH IS AN INTEGRAL PART OF COLLIER COUNTY ORDINANCE
NO. 2004-31, KNOWN AS THE COLLIER COUNTY UTILITIES STANDARDS
AND PROCEDURES ORDINANCE, WHICH IS CODIFIED IN CHAPTER 134,
ARTICLE III OF THE CODE OF LAWS AND ORDINANCES; PROVIDING
FOR A DELAYED EFFECTIVE DATE OF AUGUST 1, 2011 FOR THE
MANUAL.
Copies of the proposed Resolution are on file with the Clerk to
the Board and are available for inspection. All interested
parties are invited to attend and be heard.
NOTE: All persons wishing to speak on any agenda item must
register with the County administrator prior to presentation of
the agenda item to be addressed. Individual speakers will be
limited to 3 minutes on any item. The selection of an individual
to speak on behalf of an organization or group is encouraged. If
recognized by the Chairman, a spokesperson for a group or
organization may be allotted 10 minutes to speak on an item.
Persons wishing to have written or graphic materials included in
the Board agenda packets must submit said material a minimum of 3
weeks prior to the respective public hearing. In any case,
written materials intended to be considered by the Board shall be
submitted to the appropriate County staff a minimum of seven days
prior to the public hearing. All material used in presentations
before the Board will become a permanent part of the record.
Any person who decides to appeal a decision of the Board will
need a record of the proceedings pertaining thereto and
therefore, may need to ensure that a verbatim record of the
proceedings is made, which record includes the testimony and
evidence upon which the appeal is based.
If you are a person with a disability who needs any accommodation
in order to participate in this proceeding; you are entitled, at
17 8 '!-I
no cost to you, to the provision of certain assistance. Please
contact the Collier County Facilities Management Department,
located at 3335 Tamiami Trail East, Building W, Naples, Florida
34112, (239) 252-8380. Assisted listening devices for the hearing
impaired are available in the County Commissioners' Office.
BOARD OF COUNTY COMMISSIONERS
COLLIER COUNTY, FLORIDA
FRED COYLE, CHAIRMAN
DWIGHT E. BROCK, CLERK
By: Ann Jennejohn, Deputy Clerk
( SEAL)
Ann P. Jennejohn
178 '1-1
From:
Sent:
To:
Subject:
Attachments:
postmaster@collierclerk.com
Friday, July 08, 2011 4:38 PM
Ann P. Jennejohn
Delivery Status Notification (Relay)
ATT126538.txt; Amending Water-Sewer Utilities Standards Manual
This is an automatically generated Delivery Status Notification.
Your message has been successfully relayed to the following recipients, but the requested delivery status
notifications may not be generated by the destination.
leqals@naplesnews.com
1
17 8 ,'~ ..
Ann P. Jennejohn
From:
Sent:
To:
Subject:
Attachments:
Ann P. Jennejohn
Tuesday, July 12, 2011 9:01 AM
'Heredia, Blanca'
RE: Ad Confirmation
Amending WSD Utilities Standards Manual.doc
Hi Blanca,
The first paragraph in the title of this ad needs to be changed a little. (the one you're waiting for the o.k. on)
Hopefully there's time to do this!
I've attached a new ad (to this e-mail) but it's only the first paragraph that needs to be changed; the title and the
rest of the body are great!
Please let me know if you are able to do this.
I'm sorry about this.
Ann
-----Original Messageu_u
From: Heredia, Blanca rmailto:BEHeredia@Naplesnews.coml
Sent: Monday, July 11, 201111:20 AM
To: Ann P. Jennejohn
Subject: Ad Confirmation
Importance: High
Hi Ann, I hope this isn't a duplicate please make sure it's correct, it's going to print on July 14th.
Thank you & Have a great day!!
Blanca
239-263-4710
Ad Number
Total Ad Cost
1908647
$264.54
1
17 B . 1'.4i~
Ann P. Jennejohn
From:
Sent:
To:
Subject:
Attachments:
Heredia, Blanca [BEHeredia@Naplesnews.com]
Tuesday, July 12, 2011 9:26 AM
Ann P. Jennejohn
The top part of this notice has been changed....
UASA5EE.jpg
Importance:
High
Please let me know of any other changes.... Have a good one today!!
Blanca
Thank you for placing your ad.
Date 07/12/11
Publication NDN
Account Number 508751
Ad Number 1908647
Total Ad Cost $264.54
1
Ann P. Jennejohn
17 B
t,
From:
Sent:
To:
Subject:
NeetVirginia [VirginiaNeet@colliergov.net]
Tuesday, July 12, 2011 4:40 PM
Ann P. Jennejohn
FW: The top part of this notice has been changed....
-----Original Message-----
From: WhiteJennifer
Sent: Tuesday, July 12, 20114:39 PM
To: NeetVirginia
Cc: WiliiamsSteven
Subject: RE: The top part of this notice has been changed....
Dinny,
This is acceptable. I am baffled as to why the NDN cannot correct the spacing error in the title.
Jennifer
-----Original Message-----
From: NeetVirginia
Sent: Tuesday, July 12, 20114:30 PM
To: WhiteJennifer
Cc: WiliiamsSteven
Subject: FW: The top part of this notice has been changed....
Importance: High
Please review revised version.
Dinny
-----Original Message-----
From: Ann P. Jennejohn fmailto:Ann.Jenneiohn@collierclerk.coml
Sent: Tuesday, July 12, 2011 9:36 AM
To: NeetVirginia
Subject: FW: The top part of this notice has been changed....
Importance: High
Here's that WSD Utilities Standards Manual (ad) Dinny.
Ann
-----Original Message-----
From: Heredia, Blanca fmailto:BEHeredia@Naplesnews.coml
Sent: Tuesday, July 12, 2011 9:26 AM
To: Ann P. Jennejohn
Subject: The top part of this notice has been changed....
1
, . ... . .NOTICEOFINTENT TO CONSIDER HES~LI~JTION .. ... ,17 R f"~_
N~tlc:e ls.nerebV,9Iven ,that the Board ofc()un~YCOmmI5slon~rsofcolllerLo~t~.
w't11 hold a public he~nTLI~sday. Jul.y 26. ,20 11IntheBo.~rorQom,3rd F1oortAd.-
m... i.n..i..rt..........raJ!ion...B.U..i1d.in.9.../c. ..ier CO.....u..IT. t~..t. G...'?...,..ternmel1tce..n........JerI32~9 Tam.jami.. TF.ail.East. I
Naples, Flond.a, The mr:etlng,wlll beglnat 9:00A,M. .The tltleo"f the proposed
Resol utio ni5. (1)fol IOV\i!i:
A RESOLUTION OF THE BOARD OF COUNn" COMMISSIONERS OF COLLIER COUNTY;
FLORIDA AS EX-OFFICIO THE GOVERNING BOARD OF THE WATER-SEWER DISTRICT
t\PPROVI NAME NOM ENTS TO THE COLLIER COUNTY WP-. TER-SEVVER DISTRICT'S
UTILITIES STANDAr~DS MANUAL. WHICH IS AN INTEGRAL PART OF COLLIER COUN-
TY ORDINANCE
NO. 2004.31. KNOWN AS THE COLLIER COuNTY UTILITIES STANDARDS AND PROCE-
DURES ORDINANCE, WHICH IS CODIFIED IN CHA.PTER f34. ARTICLE IUOF THE CODE
OF LAWS AND ORDINANCES; PROVIDING FOR A DELAYED EFFECTIVE DATE OF AU-
GUST 'I. 20'11 FOR THE MANUAL
Copies oftheprOp0$ed ResQtutibrrare onfile vviththe C lerktothe Bqar<j and are
available Tor hlspedian. All it1terestedp~rtiesare invited to..attendand ~e heard.
NOTE., All personsvvi$hing.tosp~ak on any~genddi't~mm14st registt?r vvith the
C:ount}iadminirtnItor prlqrttiPT~l3rrtation of the ageooq it~m t:obe~ddrla55ed.ln-
divIdualspeakers v,tlll belimi'ted to lrnirn,Xte5 an any item. The selection of anindi-
vidual to speak .en behalf of anor~anlzation or.grollpl~en~ouraged. Ifre<:.ognlzed
by theCh:urrnan,a spokesperson Tor agrrJUp ororgamzatlon maY' be allotted 10
minutes to speak on an item..
Persons wlsll1ns to havewritterr.or...graphic materia.l& induded. tn. the Board . agenda
packets mus:tsubml't saidmat~tj.al a rnlnimumof :3 weekspri9f to the respective
p.lJ b. He." e. a..... n rI...9,...IM. CI. ,.t1 Y c. as e.... written n'.~. t. er..la.Js...... i. rrcftt1..... cJ.....t=.d .t.o ~. e.. (.0. t1SlcJ... e r...e.... d. b..Y. .t h. e...
Board shaH be$ubm11ted to the appraprlateC()l1nty!itaff amlf'umum. of se\lenday~
~rior 10 the public hearing, AU material used In presentatlons befot'e the.8oard vvill
become a permanent part of thecrecord
Any J)er~on vVhp d:etides to appeal a de(ish:>n6f.fhe\ e6~rd will tTf;sdatetonj ofth.~
~'I'o(eedin9S pettalnln$lt~e.reto anqth~re~ore, may.ne~d toel1S:Luethat averbati~l
recQrd crf the pr.p(:~dln9S Jsmi;)det'ovhlch re<:ord ul(.lud~s tllete.strmony qnOeVI-
denc€! upon whk:h the a~~eali5 based
If you are a person with a di)abilit~ vvho. needs any accpmmodatlon in order to par.
ti.cipate in this proceedIng; YOQare entit;led,atnocost l0 )fOU,to the prOVision of
cef'tainaS5ts'tanc.e.Please con'taa theColHer COlJt1tyFacilities Management .Depart-
ment/located ~t 3335 Tamlami Trail Eastf Huildin~ W, Naples. Florida 341 12. (239)
252&838(J. AS$~sted hstenin9. deVIces .tor the hearing irnpaired are availablem the
County O:'HllnlI5lSI0rlers' Office
BOARD OF 'COUNTy corlJlM1SSIONERS
COLLIER COUNTY,FLORIDA.
FRED COYLE, CHAIRMAN
DVVIGHTE.BR'OCK. CL!:RK
By: Ann Jennejoht1, Deputy Clerk
(SEAL)
July '14, 2011
N.o, 1908641
NAPLES DAILY NEWS
Published Daily
Naples, FL 34110
Affidavit of Publication
State of Florida
Counties of Collier and Lee
Before the undersigned they serve as the authority, personally
appeared Kim Pokarnev, who on oath says that she serves as
the Accounting Manager ofthe Naples Daily News, a daily
newspaper published at Naples, in Collier County, Florida;
distributed in Collier and Lee counties of Florida: that the
attached copy of the advertising, being a '
PUBLIC NOTICE
in the matter of PUBLIC NOTICE
was published in said newspaper 1 time in the issue
on July 14,2011
Affiant further says that the said Naples Daily News is a newspaper
pubhshed at Naples, in said Collier County, Florida, and that the said
newspaper has heretofore been continuously published in said Collier
County, Florida: distributed in Collier and Lee counties of Florida,
each day and has been entered as second class mail matter at the 'post
office In Naples, in said Collier County, Florida, for a period of I
year next preceding the first publication of the attached copy of
advertisement: and affiant further says that he has neither paid nor
promised any person, firm or corporation anv discount, rebate
commission or refund for the purpose of securin; this advertiseme~t for
P"bli"2~ <
( Sigliature of affiant) L---
Sworn to and subscribed before me
This 2nd day of August, 2011
KAROL E KANGAS
178
~~~\d.:
l
NonCE OF INTENT fOcONSIDERRESOLUTION ,
~~i~ol~' ~~~~~c~:::'r~~~utd~?~lvo4aF~~r'I~~:~~~~,'~~~~1J.1~~
ministration Building, Collier County Government Centerc>~lI9 Tamiall\i, rra~,~
Naples, ' Florida. The, meeting will begin at 9:00 A.M. 'ne' titIf Of the' prOpOsed
,Resolution ~.sfqlIClW$: '
A RESOLlmON IllFTHE, 80ARO OF CQUNl't COMMISSioNERS' Of COLLIER CQUNl'Y,
FLORIDA AS EX-oFFIClO TtlE !OOVE1lNIN~ BOARD OF THEWATER-SEMR DISTRICT
APl'ROVlNG AMENDMEHTS' TO THECOLI:1ER COUNTY WATER-SEWER DISTRICT'S
~'grJfNl1~DAIA5 M~\lAL.WtiICHIS ~,It+TEGRAL PART OF COLLIER ,COUN-
NO,. 2ClO4-31,KNOWNAS THE-COLUe't COUNTY UTILITIES STANDARDS AND PROCE-
QURES ORDINANCE, WHIQt JS CODifiED ,IN OiAPT.ER 134, ARTICLE III OF, THE CODE
OF lAWS ANOOROOIANtESi PflOVIOlNGFOR A QELAYED EPfECTlVEDATE OF AU-
GUST 1, 201H~llTHE foMNl,IAL '
COpies Of the: lIro~ '/leSOlutlonar., on ,.f", ,,,,,lth .thl!Cf.1t to the Board and are
available for )nspection. All interested parties ,r^ejn~ited t~ a~end and be heard.
NOTk AII.~fSons,,,,,ishl "to speak on, any. i!gencla Itemll1usj: regi~n"ittl the
'County administrator' presentation of ~he agenda .iterll to beacjdressed. I,ri-
divillual. sptllilers will ~ t93 [!l11~jq!l "" ~!I';,1IJ,,,"s(lJ!iqIIlA9f_~inCfi.
v(dual to sPe.t< on behalf , an, Org8nl~tlo~ or groop is ,ncquiajjeQ,'1f recognfzeo
by the Chairman, 'a '~k~n for a ,group' ororpnlzatlon 'maybe allotted 10
minutes to speak on an item.
Persons WJs/lingtohave written or graJ!hic mlKerials\llCluded in ~ BoJrdagenda
~ckets must ,'sUbmit ,said in,ater",liIla minimum Of 3 weeks,pr, jor to the respectiv.
public hearing.' In /lny,cese".wrMenmiterlalsl~rded to be considered by the
Board shall, ~ sull.m~oo to the aPPr:cmrI..",~nt; .stlIff a mlnilllUlll of $even claYS
C~;:~:~~~n~~~~(: ~:r~.alllsed Inp~~lonsbef~ the Board ~111
AnyPlll$On VI/Ilo /lecld\!$to appeal,a dtldston Of the: Board wRI 'neel". retord of th.
proceedings pertaining th.reto and tl!erefore, may neel to .nsure that a v.rbatim
record of the procl\eOings is mad\!, which record indudes the testimony and ev!-
d.nc;e upon whid) t~i!pjlI!aIis based. " ,. ,\ .
If you a.. a person with a disability who needs any accommodation in ord\!,r to par-
tiCipate in this proceeling; you a.. entitloo, at no cost to you, to the provision of
certain assimn(\!. PleaS\! .contact the c.olI,ier"COU" nw. F,aciliti,es, Man,ag.ment OeP..'!.~
m.nt. locatoo at 3335 Tariliami Trail. ~ ~ildjnf:W, Nllpl~ FI9"illa 34112, ,l,Z.:!~1
2S2-B3BO. Assistoo listening devices fO/' ~\'.l1lIlmpalfecl are availabl.in the
County Commissioners' Office. ,"', ~ ' '
BOARD 6Ft\')i:i~ ~~ISSI6~e'RS '
COLLIER COUNlY, FLO!lIDA
FRED COYLE, (:IiIA1RMAN
DWIGHT E: 8RO~ CLERK
By: An~ Jennejohn,Dep~C1erk
(SEAU .
luw 14 )011 Nn 1CKlAfi47
ORIGINAL DOCUMENTS CHECKLIST & ROUTING SLf4
TO ACCOMPANY ALL ORIGINAL DOCUMENTS SENT TO
THE BOARD OF COUNTY COMMISSIONERS OFFICE FOR SIGNATURE
Print on pink paper.Attach to original document.Original documents should be hand delivered to the Board Office.The completed routing slip and original
documents are to be forwarded to the Board Office only after the Board has taken action on the item.)
ROUTING SLIP
Complete routing lines#1 through#4 as appropriate for additional signatures,dates,and/or information needed.If the document is already complete with the
exception of the Chairman's signature,draw a line through routing lines#1 through#4,complete the checklist,and forward to Ian Mitchell(line#5).
Route to Addressee(s) Office Initials Date
(List in routing order)
1. Commissioner Fred W. Coyle, Board of County Commissioners
BCC Chairman
2.
3.
4.
5. Ian Mitchell, Executive Manager Board of County Commissioners Q
6. Minutes and Records Clerk of Court's Office
PRIMARY CONTACT INFORMATION
(The primary contact is the holder of the original document pending BCC approval.Normally the primary contact is the person who created/prepared the executive
summary.Primary contact information is needed in the event one of the addressees above,including Ian Mitchell needs to contact staff for additional or missing
information.All original documents needing the BCC Chairman's signature are to be delivered to the BCC office only after the BCC has acted to approve the
item.)
Name of Primary Staff Nathan Beals Phone Number 252-2583
Contact
Agenda Date Item was July 26,2011 Agenda Item Number 17 B
Approved by the BCC
Type of Document Resolution amending the Collier County Number of Original 1
Attached Water-Sewer District's Utilities Standards Documents Attached
Manual l Al 127j
INSTRUCTIONS & CHECKLIST
Initial the Yes column or mark"N/A" in the Not Applicable column,whichever is Yes N/A(Not
appropriate. (Initial) Applicable)
1. Original document has been signed/initialed for legal sufficiency.(All documents to be NB
signed by the Chairman,with the exception of most letters,must be reviewed and signed
by the Office of the County Attorney.This includes signature pages from ordinances,
resolutions,etc. signed by the County Attorney's Office and signature pages from
contracts,agreements,etc.that have been fully executed by all parties except the BCC
Chairman and Clerk to the Board and possibly State Officials.)
2. All handwritten strike-through and revisions have been initialed by the County Attorney's N/A
Office and all other parties except the BCC Chairman and the Clerk to the Board
3. The Chairman's signature line date has been entered as the date of BCC approval of the NB
document or the final negotiated contract date whichever is applicable.
4. "Sign here"tabs are placed on the appropriate pages indicating where the Chairman's NB
signature and initials are required.
5. In most cases(some contracts are an exception),the original document and this routing slip N/A
should be provided to Ian Mitchell in the BCC office within 24 hours of BCC approval.
Some documents are time sensitive and require forwarding to Tallahassee within a certain
time frame or the BCC's actions are nullified. Be aware of your deadlines!
6. The document was approved by the BCC on 07/26/201 1 (enter date)and all changes NB
made during the meeting have been incorporated in the attached document.The
County Attorney's Office has reviewed the changes, if applicable.
I:Forms/County Forms/BCC Forms/Original Documents Routing Slip WWS Original 9.03.04,Revised 1.26.05,Revised 2.24.05
17 B I.'
RESOLUTION NO. 2011 - ~
A RESOLUTION OF THE BOARD OF COUNTY COMMISSIONERS OF
COLLIER COUNTY, FLORIDA AS EX-OFFICIO THE GOVERNING
BOARD OF THE WATER-SEWER DISTRICT APPROVING
AMENDMENTS TO THE COLLIER COUNTY WATER-SEWER
DISTRICT'S UTILITIES STANDARDS MANUAL, WHICH IS AN
INTEGRAL PART OF COLLIER COUNTY ORDINANCE NO. 2004-31,
KNOWN AS THE COLLIER COUNTY UTILITIES STANDARDS AND
PROCEDURES ORDINANCE, WHICH IS CODIFIED IN CHAPTER 134,
ARTICLE III OF THE CODE OF LAWS AND ORDINANCES; PROVIDING
FOR ADELA YED EFFECTIVE DATE OF AUGUST 1, 2011 FOR THE
MANUAL
WHEREAS, on May 11, 2004, as Item 8 D. the Board of County Commissioners as the
Ex Officio Governing Board of the Water-Sewer District (Board) concurrently adopted Collier
County Ordinance No. 2004-31, entitled the Collier County Utilities Standards and Procedures
Ordinance (the "Ordinance"), and the Collier County Water-Sewer District Utilities Standards
Manual," (Manual), including all of the Manual's exhibits, and
WHEREAS Ordinance No. 2004-31 is codified in Chapter 134, Article III of the Code of
Laws and Ordinances; and
WHEREAS, since the 2004 adoption of the Manual it has become necessary to make
updates that reflect current standards in design and preparation of plans and specifications for all
utilities construction projects; and
WHEREAS, after input from stakeholders Public Utilities staff has recommended that the
Board adopt this Resolution to approve amendments to the Manual as identified in Exhibit A;
and
WHEREAS, Section 134-61 of the Code of Laws and Ordinances requires the Manual to
be amended by Resolution of the Board under the scheduled public hearings or the summary
agenda section; and
WHEREAS, it is in the interest of the health, safety, and welfare that this Resolution be
adopted.
NOW, THEREFORE, BE IT RESOL VED BY THE BOARD OF COUNTY
COMMISSIONERS OF COLLIER COUNTY, FLORIDA AS EX-OFFICIO THE
GOVERNING BOARD OF THE WATER-SEWER DISTRICT, that:
17 B .. ,,.
The Collier County Water-Sewer District Utilities Standards Manual, as amended, as
identified in Exhibit A, is hereby approved and shall take effect on the 1 st day of August, 2011.
This Resolution adopted after motion, second and majority vote, this ~ day of July,
2011.
. "
~"--6~~
Jenni;UB, White
Assistant County Attorney
\~" q.~tqf'i."
",,\' ,'." 1 (, ": 'I
..." ",u"llv,/7/c. IJ
,,:-, C;;",/'-.J ,,'::- ~ ~. <.'-.'.....
BOARD OF COUNTY COMMISSION~5 ,OF:,:GOLLIEl).":
COUNTY, FLORIDA, AS EX-OFFICI@~-~trB .GOVERNrN~_,'_
BOARD O~T E WATER-SEWERDIS~~~T':__~. .'.: c.'" ~
W ~ _.' ..
. .. ~ ~s. -... ... .'"' '"'-
y. ->;;" . .
FRED W. COYLE, CHA AN ?:'l;~'1'~'..':"~' ,.",
IIIJ L.o v'. rl1.,,'" \\"
Ill/lilll.'I""'\
Table
of
Revisions
17 8 ! till
Exhibit A
17 Bl ..
COLLIER COUNTY UTILITIES STANDARDS MANUAL
TABLE OF REVISIONS
COLLIER COUNTY PUBLIC UTILITIES PLANNING AND PROJECT MANAGEMENT DEPARTMENT
AS OF 07/2011
CHANGES TO UTILITIES
Section Sub-Section/ Detail # Revision Summary
1 1.4 Update meter requirements to only require leak detection meters on fire
service lines.
3 W-8 Add detail, previouslv deleted, and update.
3 W-9 Update detail.
3 W-9A Update detail.
3 W-1O Delete detail.
3 W-11 Add detail, previouslv deleted, and update.
3 W-11 A Update detail.
3 W-15 Delete detail.
3 W-16 Add detail, previouslv deleted, and update.
4 Appendix G Update list.
Page 1 of 1
17 B
Ira I
5t,
Proposed Revision to Section 1. DesiQn Criteria
Proposed additions in text are noted in bold.
Proposed deletions in text are noted in strike through.
Section 1, Design Criteria, Page 6, text revisions in 1.4
1.4 Fire Service Systems
All private fire service systems for sprinkler systems, wet standpipe systems, and privately-
owned or controlled distribution systems shall be metered with a Fire Service, line sized, meter
aRG-shall be installed with an appropriate back flow prevention device with a leak detection
meter. The meter shall be owned and maintained by the private service owner. The COUNTY
requires all privately-owned backflow devices to be certified at the time of installation and on an
annual basis by a Certified Back Flow Tester (University of Florida, TREEO Center, or
equivalent certification program). The results shall be submitted to the County Manager or
designee. The County Manager or designee will require all privately owned metering devices to
be certified for accuracy at the time of installation. Fire meter devices using a three quarter to
two inch (%" to 2") metering device shall be re-calibrated to manufacturer's specifications every
five (5) years, replaced every ten (10) years, or replaced immediately upon meter failure. Fire
meter devices greater than two inches (2") shall be re-calibrated to manufacturer's
specifications every five (5) years and replaced immediately upon meter failure. The County
Manager or designee will inform the owner by mail prior to the due date. Private owner(s) shall
submit certification results to the County Manager or designee within sixty (60) days of the due
date.
1.4.1 Fire Service Meters for Residential Systems
Residential projects such as, but not limited to, single family, multi-family condominiums, trailer
parks, mobile home parks, etc. utilizing a master meter shall pass all fire flow through such
meter. The meter shall be sized to pass the domestic coincident draft plus rated fire flow at the
AWWA pressure loss specifications.
1.4.2 Fire Service Meters for Commercial and Other Non-residential Systems
Commercial projects such as, but not limited to, shopping centers, malls, retail, and industrial
buildings shall pass all fire flow through a potable master meter or have a separate fire service
connection to the water distribution main. The Fire Service meter and isolation valves shall be
extended above final grade as shown in the Utilities Detail Drawings. For meter reading
purposes, metering devices shall lie within a County Utility Easement (CUE) that shall be
dedicated separately to the Board for the appropriate Water-Sewer District or in conjunction with
the easements for anyon-site utility system(s).
The Owner shall purchase and install an approved .^.MR meter ~lnd approved backflow devices
with a leak detection meter at no expense to the appropriate Water-Sewer District.
17 B ~ I'
CONCRETE FOUNDATION FULL
LENGTH OF ASSEMBLY (TYP)
4' WIDE, 6" THICK 6" x 6"
10xl0 WELDED WIRE MESH
FLOW
---
MIL POLY WRAP
ONSTRUCTION GRADE
SHEETING. DOUBLE
LAYER. PLASTIC All
PURPOSE
FLOW
CUSTOMER
SERVICE LINE
PROPER1Y OWNER MAINTENANCE
TO THIS POINT
NOTES:
1. ASSEMBLY WILL BE OWNED AND MAINTAINED BY PROPERTY OWNER, STARTING AFTER THE INLlNE GATE VALVE AT THE
PROPERTY LINE OR RIGHT-OF-WAY LINE.
2. COUNTY WILL REQUIRE DEDICATION OF MATERIAL UP TO AND INCLUDING THE INLlNE GATE VALVE FROM THE COUNTY'S WATER
MAIN.
3. BACKFLOW DEVICE REQUIRES INITIAL CERTIFICATION BY AN APPROVED CERTIFIED TESTER WITH RESULTS AND ANNUAL TEST
RESULTS SUBMITTED TO THE COUNTY WATER DEPARTMENT.
4. ALL PLANTING SHALL BE A MINIMUM OF 1.5' FROM EDGE OF SLAB, AND SHALL PROVIDE A 3' ACCESS OPENING.
5. THIS ASSEMBLY SHALL BE PAINTED WITH RED EPOXY PAINT.
W-8
REVISED: JULY 2011
17 B 1.'
2" REDUCED PRESSURE BACK FLOW PREVENTER ASSEMBLY
SUPPLIED WITH AMMONIA AND CHLORINE RESISTANT SEATS
AND SILICONE RUBBER SEALS. UL/FM APPROVED FOR FIRE
SERVICE INSTALlATION. INSTALLATION AS REQUIRED BY
COUNlY ORDINANCE AND AWWA M-14. (SEE APPROVED
BACKFLOW DEVICES. APPENDIX G)
LOCK OS&Y VALVE CLOSED
2" CURB STOP
12" SPOOL PIECE
WITH 2" TAP
FIRE PROTECTION MITER (SEE COUNlY
APPROVED PRODUCT LIST, APPENDIX F)
UL/FM APPROVED FOR FIRE SERVICE
INSTALlATION (FACTORY ASSEMBLED
WITH TOP ACCESS STRAINER ONLY)
RISING STEM AND RESILIENT SEAT
FLANGED GATE VALVE
(lYPICAL OF THREE)
MJ 45. OR 90' BEND WITH
RETAINER GLANDS
MAIN SIZE PER
UTI LIlY PLAN
MAIN SIZE PER
UTILIlY PLAN
NOTES:
1. ALL ABOVE GROUND PIPE SHALL BE FLANGED END DUCTILE IRON PIPE, PRESSURE CLASS 350. ALL NUTS AND BOLTS SHALL
BE STAINLESS STEEL.
2. WATER MAIN EXTENSION AND ASSEMBLY IS REQUIRED TO BE FLUSHED, CHLORINATED AND GIVEN BACTERIAL CLEARANCE BY
THE WATER DEPARTMENT LAB BEFORE PLACEMENT IN SERVICE.
3. BACKFLOW UNIT AND METER REQUIRES INITIAL CERTIFICATION FOR OPERATION AND ACCURACY WITH RESULTS AND
ANNUAL TESTS SUBMmED TO THE COLLIER COUN1Y WATER DEPARTMENT.
4. INSPECTIONS ARE REQUIRED FOR SYSTEM TIE-IN AND ASSEMBLY CONNECTION.
5. THIS ASSEMBLY SHALL BE PAINTED WITH RED EPOXY PAINT.
6. ALL COMPONENTS THAT COME INTO CONTACT WITH DRINKING WATER SHALL CONFORM TO NSF STANDARD 61.
TEMPORARY BACKFLOW PREVENTER AND
FIRE PROTECTION METER TIE-IN ASSEMBLY
NTS
W-g
REVISED: JULY 2011
17 B
II
I'I'---l[....-r '
t___J i ri )
..-
2" TAP ("TYPICAL
OF lWO) /
2" CURB STOP~/
(lYPICAL OF lWO)
S METER
III
UL/FM APPROVED FOR FIRE SERVICE INSTALLATION.
INSTALLATION AS REQUIRED BY COUNTY ORDINANCE
AND AWWA M-14. (SEE APPROVED BACKFLOW
DEVICES APPENDIX G)
. RISING STEM AND RESIUENT
SEAT FLANGED GATE VALVE
(lYP)
2" REDUCED PRESSURE BACKFLOW
PREVENTER ASSEMBLY, SUPPUED
WITH AMMONIA AND CHLORINE
RESISTANT SEATS AND SILICONE
RUBBER SEALS UL/FM APPROVED
FOR FIRE SERVICE INSTALLATION.
INSTALLATION AS REQUIRED BY
ORDINANCE AND AWWA M-14. (SEE
APPROVED BACK FLOW DEVICES.
APPENDIX G)
LOCK OS&Y VALVE CLOSED
2" TAP (lYPICAL OF lWO)
INSTALL INUNE GATE
VALVE AT PROPERlY
LINE OR RIGHT-OF-WAY
LINE
NOTES:
VALVE SETTER (SEE COUNTY APPROVED
PRODUCT LIST. APPENDIX F)
1. ALL ABOVE GROUND PIPE SHALL BE FLANGED END DUCTILE IRON PIPE. PRESSURE CLASS 350. ALL NUTS AND BOLTS SHAL
BE STAINLESS STEEL.
2. WATER MAIN EXTENSION AND ASSEMBLY IS REQUIRED TO BE FLUSHED, CHLORINATED AND GIVEN BACTERIAL CLEARANCE BY
THE WATER DEPARTMENT LAB BEFORE PLACEMENT IN SERVICE.
3. BACK FLOW UNIT AND METER REQUIRES INITIAL CERTIFICATION FOR OPERATION AND ACCURACY WITH RESULTS AND
ANNUAL TESTS SUBMITTED TO THE COLLIER COUNlY WATER DEPARTMENT.
4. INSPECTIONS ARE REQUIRED FOR SYSTEM TIE-IN AND ASSEMBLY CONNECTION.
5. THIS ASSEMBLY SHALL BE PAINTED WITH RED EPOXY PAINT.
6. ALL COMPONENTS THAT COME INTO CONTACT WITH DRINKING WATER SHALL CONFORM TO NSF STANDARD 61.
FIRE PROTECTION METER TIE-IN ASSEMBLY
NTS
REVISED: JULY 2011
178
..
~INSTAll INLlNE GATE VALVE
AT PROPERlY LINE OR
RIGHT-OF-WAY LINE
.' .
/4>1
CONCRETE FOUNDATION (IYP) FUll lENGTH
OF METER ASSEMBLY; 4' WIDE, 6" THICK
REINFORCED 6 X 6 10/10 WELDED WIRE MESH
FIRE PROTECTION METER (SEE COUNlY APPROVED
PRODUCT LIST, APPENDIX F) WITH BYPASS. Ul/FM
APPROVED FOR FIRE SERVICE INSTALLATION (FACTORY
ASSEMBLED) (WITH TOP ACCESS FACTORY APPLIED
FUSION BONDED EPOXY COATED STRAINER ONLY)
AIR RELEASE VALVE (SEE
COUNlY APPROVED PRODUCT
LIST. APPENDIX F)
BRASS NIPPLE
REDUCED PRESSURE BACKFLOW PREVENTER
ASSEMBLY SUPPLIED WITH AMMONIA AND
CHLORINE RESISTANT SEATS AND SILICONE
RUBBER SEALS. Ul/FM APPROVED FOR
FIRE SERVICE INSTALLATION. INSTALLATION
AS REO BY COUNlY ORDINANCE AND
AWWA (SEE APPROVED BACKFlOW
DEV APPENDIX G)
ING STEM AND RESllENT
T FLANGED GATE VALVE
(lYP)
12"
NSTAll INLlNE GATE
VALVE AT PROPERlY
LINE OR RIGHT-OF-WAY
LINE
MAIN SIZE PER
UTlLlIY PLAN
MJ 45' OR 90'
BEND WITH MJ RETAINER GLANDS
(IYP)
NOTES:
MAIN SIZE PER
UTlLlIY PLAN
1. ALL ABOVE GROUND PIPE WILL HAV
SHALL BE STAINLESS STEEL.
2. (4) VEHICULAR GUARD POST
DOCUMENTS SUBMITTED F
R. CONFIGURATION TO BE ILLUSTRATED ON CONSTRUCTION
3. TIES REQUIRING CONTINUOUS WATER SERVICE MAY WISH TO INSTALL
S. (SEE W-15)
4. PROPERlY OWNER, STARTING FROM THE FIRST ISOLATION VALVE PRIOR
5. OF THE MATERIAL UP TO AND PRIOR TO VALVE ON THE ASSEMBLY FROM THE COUNlY'S
6. AL CERTIFICATION BY AN APPROVED CERTIFIED TESTER WITH RESULTS AND ANNUAL TEST
COUNIY WATER DEPARTMENT.
7. ALL PLANTINGS SHAll BE A MINIMUM OF 1.S' FROM THE EDGE OF SLAB, AND SHALL PROVIDE A 3' ACCESS OPENING.
8. THIS ASSEMBLY SHALL BE PAINTED WITH RED EPOXY PAINT.
9. ALL COMPONENTS THAT COME INTO CONTACT WITH DRINKING WATER SHALL CONFORM TO NSF STANDARD 61.
10. REFER TO APPROPRIATE SPECIFICATION IN MANUAL FOR GATE VALVES AND APPURTENANCES.
FIRE SYSTEM ASSEMBLY DETAIL
NTS
W-10
REVISED: JANUARY 2009
17 B
. ~l~A.
(iii!1'
0::1~
0::1
~~
::11:=
~IJ.
0::10
wi
c..~
Ou
8:10::
I
I
STRAINER (TOP ACCESS FACTORY APPLIED
FUSION BONDED EPOXY COATED STRAINER
ONLY). UL L1STED/HA APPROVED
AIR VALVE WITH CORPORATION STOP:\
(SEE COUNTY APPROVED PRODUCT
LIST. APPENDIX F)
BRASS NIPPLE
12" SPOOL PIEC
CONCRETE FOUNDATION (1YP) FULL LENGTH OF
METER ASSEMBLY; 4' WIDE, 6" THICK REINFORCED
6 x 6 10/10 WELDED WIRE MESH
INSTALL INLlNE GATE VALVE
AT PROPERlY LINE OR
RIGHT-OF-WAY LINE
AIR VALVE WITH CORPORATION STOP (SEE
COUNTY APPROVED PRODUCT LIST, APPENDIX F)
DOUBLE CHECK DETECTOR BACK FLOW
PREVENTER ASSEMBLY SUPPLIED WITH
AMMONIA AND CHLORINE RESISTANT
SEATS AND SILICONE RUBBER SEALS.
UL/FM APPROVED FOR FIRE SERVICE
INSTALLATION. INSTALLATION AS
REQUIRED BY COUN1Y ORDINANCE AND
AWWA M-14. (SEE APPROVED
BACKFLOW DE.VlCES, APPENDIX G)
(FlANGED GATE VALVE WITH RISING
STEM AND RESILENT SEAT (1YP)
12" SPOOL PIECE
INSTAll INLlNE GATE VALVE
AT PROPER1Y LINE OR
RIGHT-OF-WAY LINE
". ...
....." ~ .~. ." ". ... . j. .... .
ADJUSTABLE STAINLESS
STEEL PIPE SUPPORT
STANDS AS REQUIRED
ANCHORED TO PAD (1YP)
,
MAIN SIZE PER)
UTILIlY PLAN
MAIN SIZE PER
UTILIlY PLAN
MJ 45 OR 90 DEGREE BEND
WITH MJ RETAINING GLANDS (1YP)
NOTES:
1. ALL ABOVE GROUND PIPE Will HAVE FLANGED END DUCTILE IRON PIPE, PRESSURE CLASS 350. ALL NUTS AND BOLTS
SHALL BE STAINLESS STEEL.
2. (4) VEHICULAR GUARD POSTS TO BE INSTALLED AROUND ASSEMBLY. CONFIGURATION TO BE ILLUSTRATED ON
CONSTRUCTION DOCUMENTS SUBMITTED FOR REVIEW AND APPROVAL.
3. AS THIS UNIT WILL REQUIRE PERIODIC TESTING, FACILITIES REQUIRING CONTINUOUS WATER SERVICE MAY WISH TO
INSTALL PARALLEL UNITS TO PREVENT SERVICE INTERRUPTIONS.
4. ASSEMBLY WILL BE OWNED AND MAINTAINED BY PROPERTY OWNER, STARTING AFTER THE INLlNE GATE VALVE AT THE
PROPERTY LINE OR RIGHT-OF-WAY LINE.
5. COUNTY WILL REQUIRE DEDICATION OF MATERIAL UP TO AND INCLUDING THE INLlNE GATE VALVE FROM THE FROM THE
COUNTY'S WATER MAIN.
6. BACKFLOW DEVICE REQUIRES INmAL CERTIFICATION BY AN APPROVED CERTIFIED TESTER WITH RESULTS AND ANNUAL
TEST RESULTS SUBMITTED TO THE COUNTY WATER DEPARTMENT.
7. ALL PLANTING SHALL BE A MINIMUM OF 1.5' FROM THE EDGE OF SLAB. AND SHALL PROVIDE A 3' ACCESS OPENING.
B. THIS ASSEMBLY SHALL BE PAINTED WITH RED EPOXY PAINT.
W-11
REVISED: JULY 2011
178
'.
FLANGED GATE VALVE~
WITH RISING STEM AND
RESILIENT SEAT (1YP)
~
DOUBLE CHECK DETECTOR BACKFLOW PREVENTER
ASSEMBLY SUPPLIED WITH AMMONIA AND CHLORINE
RESISTANT SEATS AND SILICONE RUBBER SEALS. UL/FM
APPROVED FOR FIRE SERVICE INSTALLATION. INSTALLATION
AS REQUIRED BY COUN1Y ORDINANCE AND AWWA 1.1-14.
(SEE APPROVED BACKFLOW DEVICES, APPENDIX G)
VEHICULAR GUARD POST (1YP)~
[l:1~
ol::J
~I~
::J;;::
I
~1l:5
wll
g,1~
[I:!:2
0..[1:
I
I
INSTALL INLlNE GATE VALVE
AT PROPER1Y LINE OR
RIGHT-OF-WAY LINE
;;::
o
-'
lL.
CONCRETE FOUNDATION (1YP)
4' WIDE x S' LONG. 6" THICK;
REINFORCED 6 x 6 10/10 WELDED
WIRE MESH
.". 4'
. ..:
4' ......A.
,'~' . ',.d' . .
.. .
"':',
4'
NOTES:
VALVE SETTER (SEE COUN1Y APPROVED
PRODUCT LIST, APPENDIX F)
1. ALL ABOVE GROUND PIPE WILL HAVE FLANGED END DUCTILE IRON PIPE. PRESSURE ClASS 3S0. ALL NUTS AND BOLTS SHALL
BE STAINLESS STEEL.
2. (4) VEHICULAR GUARD POSTS TO BE INSTALLED AROUND ASSEMBLY. CONFIGURATION TO BE ILLUSTRATED ON CONSTRUCTION
DOCUMENTS SUBMITTED FOR REVIEW AND APPROVAL.
3. AS THIS UNIT WILL REQUIRE PERIODIC TESTING, FACILITIES REQUIRING CONTINUOUS WATER SERVICE MAY WISH TO INSTALL PARALLEL
UNITS TO PREVENT SERVICE INTERRUPTIONS.
4. ASSEMBLY WILL BE OWNED AND MAINTAINED BY PROPER1Y OWNER. STARTING AffiR THE INLlNE GATE VALVE AT THE PROPER1Y LINE
OR RIGHT-OF-WAY LINE.
S. COUN1Y WILL REQUIRE DEDICATION OF MATERIAL UP TO AND INCLUDING THE INLlNE GATE VALVE FROM THE COUN1Y'S WATER MAIN.
6. BACK FLOW DEVICE REQUIRES INITIAL CERTIFICATION BY AN APPROVED CERTIFIED TESTER WITH RESULTS AND ANNUAL TEST RESULTS
SUBMITTED TO THE COUN1Y WATER DEPARTMENT.
7. ALL PLANTING SHALL BE A MINIMUM OF 1.S' FROM THE EDGE OF SLAB, AND SHALL PROVIDE A 3' ACCESS OPENING.
8. THIS ASSEMBLY SHALL BE PAINTED WITH RED EPOXY PAINT.
HAZARDS. AS DEFINED BY AWWA 1.1-14 (e.g.. RISK
R, ETC.). EXIST.
17 B t.
~3Q: ....: -J
~ Z
~en~ v W ~
9 ~ ~,.... w~ Q:~ W ~
. Lt... 0 ~!zo It:> N::! ~~ 0
O)-wl=' litJ ~<w ~x -I- :::l W ~
-J ~OOQ:!,2 1ni';~<C5 en~ enCl.. Lt... Q:
-J zoG:g: ::J~ ZQ:Z Ww ~ ~
~ Q:-Q: ~z 1-0 ~
~ww!a wf3&Z w ~w::5 OQ: en ~ Z
Ii:' tJz !zQ:<~<& Cl..Cl.. w 0
I-!:::!OO !:!!w 0 -J U
~ en5w ~o ww~:5o< Lt...I- z ~
0- ~~ < -J
eJwoQ: ~~ GJz Lt...-J::i vi -J
Iii t:>ooQ:- Q:c::.......j5 w w ai ~ <
Q: Cl..Lt... Cl..< Cl..o-JenWu u~ ::5 Q: I
0 ::5g~fu oln ~:E~~~~ 0 en
Cl.. O~ en
WZ gu~ ~O ~O ~ Q:
0 ~Q:Q:O >- Lt... W
Q: ~WWW OW ~~i5:zC5~ ou 0 z !;{
< t;:jWQ: Q: ~
~ W~~5 Q: 8:!,2 ~<en~~g Cl..W ~
t:> W Cl..>,.... Cl..I
Q:~~8 t;:j <eJ~ ooZQ::5~~ <I- W t:>
G:OWQ: ~ OW-J zO 00 z
< ~enz ~~oo<Z~ S2
C5 ZWO ~~~In~oo <I- z e,;
~Q:Q: ~IQ:~80 >-: c:: z
OG:W 0 ~
u z ~!:::WW)-~ I 0
W~~ Cl..~i5!,2oo~ !::: u
~Lt...Iii 00!,26;0Cl.. ~ ~
.......0 ~~ijj~~~
enwen 0
~Cl.. ~ Cl..
Q:>en fag,~~8l::J W
WOW
t;:jQ:U Q:en < G:Q:,e 0
Cl..U W
~Cl..< 0 (/)~
< Z
Z~~ 0 Ck:
QLt...I- 00 w
tJ::'-I I ~ I-
W z
~~!::: ~ 0 W
o ~ <W 0 Vi CD :::!:
Q: ........ Cl.. U ~ :::!:
Q..h:'S wO Lt...
00 ~ w=
~~~ en W (/)00
-Jen 0 ~
G:Ooo -J W III
z~ ~U z en~ <{-l
-JWW en~ ~ I-lD
<Cl..en 0 -J <{
1S~~ Q: Zo -J Ck:=>
t:>" t:> WQ: <
Zl"l ci Z< I WCl
~< Ww 00 en I-
i';Q: Cl..Z
::5W 8~ Q: W
~~ W :::!: Z
Cl..Q z
> ~ ...J<{
-JO -JLt... -JLt...
-JQ: ;iiJj -Jen Iii <{:::!:
<Cl.. <Z
..j. ..0 .0 ....: rxi =>W
ClCk:
en WLa...
z !z ~ U=
0 ow Ww
Q: Q:~ Zz
-W W~ ~- >0
WOO t;:jU O-J Ck:
-J ~O ~~ W
i=::J 0 III Ck:
U< 0
~I Zz WW W
Oen ~O Cl..Cl.. W >
00
0 ~!J ~~ Q:Q: Ck: 0
0 <~ Cl..Cl.. La...
~t:> 0 OQ: )-w I
:s:~oo~ 000 wlii oo~ I-
W :::lz
.z t:>~ 01-
0- ~8 . ~
0> ~ Ii:' ~~ w<
~w
Q:Q:~ zz<i ~~
~ o ....... ;;:;o~
9 Ln~~ WZ -~
~:::l oooQ: ~
. Lt... vEz wCl..
W o)-wl=' < ~~~ o~
~ ~OOQ:!,2 ...,~::5 :::l
~ t:> ::it:>
~Q: zoG:g: ~ci ~liio
wow ~ww!a ll'l en~z OW
I-!:::!oo wl"I o:::l< w~
!;{wz en5w Q,en Cl..- ~g~
t:>~::J ~~ ow~
-J eJwoQ: ~~ ow::J
W )- t:>ooQ:- Q:OO-
~~~ Q: Cl..Lt... t:>w1 zu <OGJ ~~~
::5g~fu w~1- ~w..J ~I-Q:
2!eJJ. zQ:Iw -JQ:~
::JCl..Qz oQ:w Q:zQ:
-Cl.. ~Q:Q:0 Q:~w -Jwl
-Joo Z Q:::J t:>enlii ::50~ -t;:Lt...
-JQ:I ~www -I-
~Cl..~ t;:jwQ: -J<Q:)- wf3en ~~ ~<9
w~~5 -Jwo~ i';Q:en u 0 ~t:>~
-~~
~!;{c:: !!:::!:~8 ~~WI ooCl..~ GiQ_ oozt:>
Lt...OWQ: ~~~::s < "z >Lt...~ ~I=-
U) w- zoo wQ:Q:
w :::lQ,~ ~8~ ~~~
3NIl )..lfM .:10 IH~I~ I- <Cl..
~o 3NIl A.1~3dO~d 0
z N ...;
W-15
REVISED: JANUARY 2009
w
U
O::~
Wo
t;J
::;::=
o
Vl...J
~~
ll..U
fu~
vO
.......z
1')<
::I ~
::> w
LL. 0::;:
'ii:'~~~
~~15~
.........w LL Q
ZVl;!!;W
Q~~g
I-: w
~ffi ~:=
~t;J~0
~::;:F'::::'
LL.'0
Wo<D~
t;J::ew~
0::1- 0
~~~ x
8~io~
o
w
~
~O::
wow
!;;:wz
~Z::J
::J
w >-
;!!;~~
~ffi.1
-ll..~
...JOO
...J0::1
j5ll..~
Vll-~
;!!;<O::
o::~p
~:>~
woO::
::;:O::tii
<ll.._
- 0
00
I-W
bo::Q:
~wLL.
Z~fu
:f~0
I-ww
ffifu~
~ 0
O::ow
:)wO::
z!::!:=
_VlO
<W...J
::;:lDLL.
WOW
Q:I-Q:
LL.......LL.
o
w
NW
~Vi~fu
1-~~G3
0::0ll..Q:
~ t:.~ 5
0:: wp
:)ffio::o::u
zt;J~:=o::
-::;:;!!;otii
~ ~~~ 0
w www
Q:b)-O::Q:
LL.~lDr;:LL.
ll..X
00
tii~
zll..
Q~
~ .
o~
ll.....J
0::1-
ou
u::>
o
. 0 E~
~'. '::= ll..
.. .4.....
wo
~~
~~
o::ll..
_ll..
<<
0::
w
t;J
::;:
~
o
w .
UVl
owzW
zu<u
~<~;!!;~
lD~wlEo
2ij:;5VlO:=
~Vl~~~
o::!z ::>t5
~~158~
z-LL.
~fnofuG3
WO::W >
g:wE>G3~
ZO::O::ll..
:=O::&:5ll..
33<8<
LL.::e::;:o::W
t5ULL.Vl~
iJ1!0::;.<......
~::>zv
0:: .07
~~~~::;:,.....
1rlo ~d ~
I-::;:Vl<~X
W::;: t-:;=-
o<ffi~<~
:'::::e lD- w
Ul::lD .~&:
~:=::>z<<
u 0::0
ow~
~~z:3
lDll.. 0<
::>ll..~tii
g~17i;!!;
0::
w W
~VllDo:i
Vl<~:)
VlVlZVl
fn~::;:o
...J<::>I-
;!!;tii::;:o
~I-~~
0::::;:0
wO ::e
ffi&:ci~
<::>w<
tiiVlQ:
::>w::>tci
""ll..o
~ii:~1I
w~
N;!
-I-
Vl::>
zo::z
<{w:)
::;:ll..ll..
.
!Xl
i~~~
Vi::;: ~ ~
~~ Vl 0
o u
G3~ !z'ii:'~ 1
::JVlW)-Vl"""
ll..::J ;!.t:.......LL.
~...J fnw ll..~
::> 0:: > 00.
~ s:- 0 ~ tii ~ ~ffi
0,-, z ll.. ~lD -1t,~
b z < w is ~ lD ~Q 0>,
Lt 0 ::;:!;;: i= . E ~ ~u~
Vl ffi ~ ~ ~ tii := Vl (,)~..yo
VlzVlOO::JwO 0
w - W ll.. ~z
U~~~O::I-::><
U Zz ou
< Vi <S:: u::> <3:.::
-oJ 0 U
ll..0 O::LL.::eo wo
ow 1::0:: O::U
.t:.!;;: :=ll.. ~w
0::8 wo Vl~
~ ~ ~ ~~
- ~ ~ 0 ll..~
~ 0 g:
I- ll.. Q: ll..
VlW <<
::e
I:: z
:= 'ii:' :)
o~ ll..
~......~
lDVl~
.~i=
g:) ::>
O::~ ffi
00:: D.
'Ww
tOZ N
v< _
"" tj Ul
::;:0:: z
~
3NIl )"VM-.::JO-lH~l~
- -~O 3NIl )..[~3dO~d --
...J ~O:: >-
...Jw W wo~~
j5zw> ll..w::e w
Ul::J!;;::.tI-~ZS!J.z
;!!;;!!;~><ll..::JO::O::J
~
17 B
w
.-: 0
z :>
w 0
O::~ 0::
ll..
WO::
tiio: ...J
...J
Ww :f
1-0
00:: Ul
!:!:!w 0
!!::!;;: z
li:::= <
w ai
u~ :)
OZ Ul
w::>
>0 LL.
ou 0
0::
ll..W w
ll..::e ~
<I- 0 .-:
~~ w z
w ~
)-0 ::e
lDW I- ~
zl:: ::;:
0 0
0::;: 0:: ll..
~~ LL. W
UVl if! 0
w
~~ 0::
LL. ::e
w::> 0 I::
UUl :=
w
...JO:: ::;: 0
~tii ::>
::;: w
I-
Zw Z Z
-I- 3j ~
Ul...J
w< < w
Q:::>
::>z w lD
oz lD'
~ ...J
w< ...JZ ...J
0:: ...Jz :f
0 <w
wz ::ell.. Ul
u< UlO
~Vl ~Vl ~
o~ lD
;!!;Ul ::;:
:=::> !Z~ w
ofn Ul
~O:: :)~ ~
ll..
:'::::e ...J;'" Ul
~I:: ...J I
lD:= << I-
ll'i tci .....:
z ~~ ~
0 Ww
::;:w Zz 0::
Q:w w::;: 15::J w
wlD Ul::> o!;;:
:::!::J ~g ~~ ~~
b:f 00 O::w oY'
~Vl Zz Wll..
::>0 ll..o I-~
~~ ~i= 00::
g:ll.. ll..::>
<u ::>0
::>
Wo 00:: )-w ...JU
OlD wtii lDF ~w
Wo ::Iz G3!;;: O::::e
~z ~8 wI-
z<( !;;:
:)Vl ~w ::;:::;:
;!!;z-i g~ 0
LL.5 wo~ ::;e:
Wz -~
~::I lDOO ~w ZW
wO::
Ol-ll.. o~
;j~ I-~ll.. o!;;: ~~
1-< ~~
UlUlO U
:=0 tiijZ OW OW
to
wI') o < w;!!; w!;;:
Q:Ul ll.._ z...JLLi o~
~~ ow15 :=;!!;z Ww
o::lD- ow::J Q:z
zu <oi;j ~F~ ::>::J
::>w-i 1:51-0:: oz
...JO:::= w-
oO::w o::zO:: O::w
O::::>~ ...Jwl
~Ul :)Q~ -t;:LL. ::IF
wfnUl ::>~ :=<7 ~~
U 0 ~~~
>o::Ul _::>w ~3
gll..~ [5S!l:: lDZ~
< .z >LL.::;: a5~o:: z::> '
::I~~ ZlD ~~15 ::>...JZ
"""0::> 8~~
<ll..Ul ~UUl
N n ..j.
W-1 6
REVISED: JULY 2011
'"
-I~~
z
o
I-
U
I.LI
Ul
(f)
W
f-
a
z
17 B 1_,
Approved Backflow Devices
VENDOR
SIZE
MODEL NO.
TYPE
USE
Ames 1 Watts 3/4" - 2" 400B 1919 RP Residential or commercial potable
water locations
Watts 3/4" - 2" 909-009 Series RP Residential or commercial potable
water locations
Wilkins 3/4" - 2" 975 RP Residential or commercial potable
water locations
Ames 1 Watts 2.5" - 10" C-400 1 957 RP Large size meter - potable water for
commercial or residential applications
Watts 2.5" - 10" 909 RP Large size meter - potable water for
commercial or residential applications
Wilkins 2.5" -10" 375 RP Large size meter - potable water for
commercial or residential applications
Ames I 4000B-LBV Combo services: fire and domestic
3/4" - 2" RP
4000B-FP lines
Watts 3/4" - 2" 009LF RP Combo services: fire and domestic
lines
Wilkins 3/4" - 2" 975XL (w/OS&Y only) RP Combo services: fire and domestic
lines
Ames Colt 2.5" - 10" C-400 (w/OS& Y only) RP Combo services: fire and domestic
lines
Watts 2.5" - 10" 909 (w/OS&Y only) RP Combo services: fire and domestic
lines
Wilkins 2.5" -10" 375 RP Combo services: fire and domestic
lines
Ames Fire Lines - Standard
2" 3000B DCDA
Watts Fire Lines - Standard
2" - 3" 007 DCDA
Wilkins Fire Lines - Standard
2" 950XL rDAF DCDA
Ames Fire Lines - Standard
2.5" -10" C300/M300 DCDA
Watts Fire Lines - Standard
3" - 10" 709 DCDA
Wilkins Fire Lines - Standard
2.5" - 12" 350 DCDA
Wilkins Fire Lines - Standard
4" - 10" 450 (N-Shape) DCDA
Note: All fire ~ine Backflow Devices shall be UL or FM approved for fire service installation. Above is a small list, others
may be used If requirements are met and information is provided
Appendix G
Rev. 07/2011