FPL Specifications for Precast Transformer Location WR#5618445
R719
FPL
SPECIFICATIONS FOR PRECAST TRANSFORMER LOCATION
WORK REQUEST:5618445 DATE:July 7,2017
NAME OF CUSTOMER:Sue Zimmerman,Collier County
PROJECT:NERDC
ADDRESS: 14700 Immokalee Road,Naples, FL 34120
FPL REPRESENTATIVE:Anna Smith Bradley TELEPHONE:239-947-7374
SECONDARY DELIVERY VOLTAGE:277/480 V.three phase
CUSTOMER AGREES TO:
I.GENERAL:
1.1 Provide a suitable location,compacted and level to 3"below final grade,for FPL transformer pad and install
secondary/service from pad to building as specified on the attached Exhibit"A"and as outlined below.
1.2 It is further understood and agreed that subsequent relocation or repair of the FPL system,once installed,will be paid by the
customer if said relocation or repair is a result of a change in the layout or grading by the customer or any of the customer's
contractors or subcontractors from the time the underground facilities were installed;and that subsequent repair to FPL's
system,once installed,will be paid by the customer if said repair is a result of damage caused by the customer or any of the
customer's contractors or subcontractors.
1.3 Notify general contractor,electrical contractor and appliance suppliers of the service voltage to be supplied by FPL.
2 EASEMENTS:
Provide FPL with good and sufficient recorded easements,including legal descriptions and survey work to produce such
easements,for the installation and maintenance of its electric distribution facilities must be granted or obtained,at no cost to
FPL,prior to FPL's energizing its facilities.
3. SITE REQUIREMENTS:
3.1 GRADE:within the easement,fill or cut to within 6"of final grade,provide grade stakes and clear easement of trees,
stumps,construction material,and other obstacles before and during construction by FPL or FPL contractors.
3.2 COMPACTION:after FPL or its contractor has backfilled the trench using rough-grading techniques,the customer is
responsible for providing compacting or other special backfill.FPL will not be responsible for settling of the trench route.
3.3 PLANS:provide FPL with location and depth information and/or drawings of all existing or proposed underground facilities
on the customer's property.Locate or expose underground facilities when requested by FPL.
3.4 NOTIFICATION:provide FPL with at least three(3)weeks notice prior to the commencement of paving,landscaping,
sodding,sprinkler systems and other surface work.Customer will bear the cost of restoring these obstructions to their
original condition if above notice is not provided.
4. TRANSFORMER PAD LOCATION:
4.1 LOCATION:pad will be installed at grade level and located at NERDC.See Exhibit"A"for exact location of precast
concrete pads,handholes,and conduit trenches.
4.2 CLEARANCES:a minimum clearance of three(3)feet must be maintained at side and rear of transformer pad and eight(8)
feet in front of transformer pad as shown on the attached drawing DCS UN-2I.This clearance applies to all types of
obstructions including landscaping and fences.
4.3 PROTECTION:provide and install curbs and/or protective barriers,when required,as detailed on DCS UN-21,after the
installation of concrete pads and transformers.Curbs and/or barriers must be in place prior to FPL energizing the service.
\ 1
WR k 5618445
8719
FPL
5. CT METERING:
When metering current transformers(CT's)are required,they will be located as specified on the attached Exhibit"A"and
installed by FPL.The customer will provide and install a I-1/2 inch galvanized conduit from the meter cabinet to the
location of the CT's.Conduit run is not to exceed 10 feet in length between CT's and meter with no more that two(2)90
degree bends unless pre-approved by FPL.Conduit pull outlet boxes(LB's)are not to be used.
6 SSDR METERING:
If solid state date receiving(SSDR)metering is required,the customer will provide and install facilities for the SSDR
metering equipment as detailed on the attached"Customer Requirements for SSDR Metering Equipment"sheet.
7. CUSTOMER SERVICE ENTRANCE:
7.I GENERAL:provide and install secondary/service to padmounted transformer from electrical equipment/meter room.
7.2 CONDUITS:the maximum cross sectional area to be occupied by the customer's service conduits is limited to the area given
in the attached Exhibit"A".Terminate conduits in pad at three(3)inches above final grade.All conduits for future services
must be installed at this time.
7.3 CONDUCTOR:the service conductors are to be limited to a maximum of eight(8)per phase at each transformer.Provide
ten(10)feet of cable beyond conduits for connection to FPL facilities in transformer compartment.Maximum size of
conductor is 750 MCM AL or 600MCM CU.
FPL AGREES TO:
I. Provide conduit(except under buildings),handholes,concrete pads,padmounted transformers,and primary and secondary cable.
2. Provide and install ground rods at transformer.
3. Provide electronic markers for customer's installation when required.
4. Connect customer's service cables to FPL facilities in transformer compartment.
5. Provide and install metering wiring between meter cabinet and CT's where applicable.
6. Maintain all equipment and material installed by FPL.
IMPORTANT:
This specification is based on the customer's submitted plans and any changes in these plans may result in additional costs,
which the customer agrees to pay. When required,the customer agrees to pay a contribution for the differential cost between
overhead and underground service.The agreement and requirements as outlined in this specification,Exhibit"A",and all
attachments MUST be adhered to.Any non-conformance or changes may result in delays until these specifications are met.
Any changes or variations from these specifications must be submitted to and approved by FPL in writing.
0
.,•' WR#561/3445
R7I9
FPL
ACCEPTANCE OF SPECIFICATIONS:
I hereby certify that I am authorized to accept these specifications on behalf of the customer and that I will deliver a copy of
these specifications to the customer and all affected contractors:
REPRESENTING THE CUSTOMER:
Andy Solis
NAME:
DATE: •a 1 a-11�$
TITLE: Chairman
TELEPHONE NUMBER• ,% 5• i/ffr/„
SIGNATURE: ,i
I hereby certify that I am authorized to accept these specifications on behalf of FPL:
REPRESENTING FPL:
NAME:Anna Smith Bradley
DATE:July 7.2017
TITLE:Associate Engineer
TELEPHONE NUMBER:2 9-947-73 4
SIGNATURE: • •
Approved as to form and legality
MAO At'a4/111611V Assistant County Atti ey 0.1
Attest as to Chairman's ,1