Carlton Lakes Unit 3-ADATE:
TO:
FROM:
RE:
MEMORANDUM
September 13, 2001
Maureen Kenyon, Supervisor, Clerk to Board
Shirley Nix, Engineering Technician II.~
Project Plan Review
Carlton Lakes, Unit 3-A
Water and/or Sewer Facilities Acceptance
On ,~- I t~r~ , 200_ The Board of County Commissioners
granted-final acceptance of the water and/or sewer facilities
within the above-referenced project.
Attached, please find the following recorded documents, in order:
1. Utilities Facilities Subordination, Consent and Joinder
2. Bill of Sale
3. Utilities Facilities Warranty Deed
Also, please find attached the following documents for your
files.
4. Owner's Affidavit
5. Attorney's Affidavit
6. Copy of preliminary approval letter from Engineering
Review
7. Engineer's final payment confirmation
8. Certification of pressure testing of water lines by
Engineer of Record
9. Bacteriological clearances (DER certification) for
water facilities
10. DER Placement-in-Service letter for sewer facilities
11. Contractor's Final Release of Lien
12. Lab results on bacteriological test for water lines
Memorandum to Maureen Kenyon, Supervisor, Clerk to Board
Carlton Lakes, Unit 3-A
Page Two
13.
Verification of final cost (Detailed: quantities,
sizes, unit cost, total cost, etc.)
14.
Letter by Engineer certifying that all water and/or
sewer facilities are located within the public
right-of-way or dedicated easements
15.
Contractual Guarantee for material and workmanship for
a period of at least one year after the Board of County
Commissioners' acceptance for both water and sewer
facilities
16.
Payment of water usage, laboratory and administrative
charges for filling, flushing and bacteriologically
certifying water lines from invoice prepared by the
Utilities Division
17.
Letter from fire district regarding ownership and
maintenance of fire hydrants and certification of field
fire flow capacity testing
18.
Certification of the inflow/infiltration test for the
sewer lines by Engineer of Record
19.
Coating certification of man holes, wet wells and dry
well from manufacturer
20. Copy of video tape test report
21.
Letter from Compliance Services section certifying that
the final inspection reveals that the Utility
facilities have been constructed in accordance with
County ordinances and regulations
If you have any questions, please call and advise accordingly.
attachments
doc:2094-2
Dwight E. Brock
Clerk
County of Collier
CLERK OF THE CIRCUIT COURT
COLLIER COUNTY COURTHOUSE
3301 TAMIAMI TRAIL EAST
P.O. BOX 413044
NAPLES, FLORIDA 34101-3044
ORIGINAL
OFFICIAL RECEIPT
When Validated
BY: PATRICIA KD
DEPUTY CLERK
RECEIPT: 3524182
NAME :
PAYOR:
REFNC:
SHIRLEY NIX/ENGINEERING
BCC (113 138312 63 64903
PD: 3 DOCUMENTS
DOC TYP FILE ID BOOK PAGE
SUBORD 2861180 2896 3096
B SALE 2861181 2896 3099
DEED 2861182 2896 3102
DESCRIPTION
RECORDING OF LEGAL INSTRUMENT
P.R.M.T.F. RECORDING FEE
INDEXING
DOCUMENTARY STAMPS - 70
DOCUMENTARY STAMPS - 35
INTANGIBLE TAX SALES
COPIES
MISCELLANEOUS FEES
INTANGIBLE PENALTY
INTANGIBLE INTEREST
RECORDING DEPOSITS
REFUNDS
AMOUNT
39.00
6.00
.7O
DEPT: RECORDING
TOTAL DUE:
45.70
PaGe 01 of 01
Prepared by and return to:
C. Perry Peeples, Esq.
Annis, Mitchell, Cockey, Edwards & Roehn
8889 Pelican Bay Blvd., Suite 300
Naples, Florida 34108
2861180 OR: 2896 PG: 3096
RECORDED in OPPICIAL RECORDS of COLLIER COUNTY,
09/24/2001 at 03:04PM DWIGHT E, BROCK, CLERK
REC PEE 15,00
Retn:
SHIRLEY NIX/ENGINEERING REVIEW
HORSESHOE DRIVE
UTILITY FACILITIES SUBORDINATION, CONSENT AND JOINDER
This Subordination, Consent and Joinder, given this Q-,~:T~ day of ,.Yr~tt~2~r~Y ,
2001, by FIRST UNION NATIONAL BANK, N.A. (hereinafter referred to as "Mortgagee"), in favor
of the BOARD OF COUNTY COMMISSIONERS OF COLLIER COUNTY, FLORIDA, AS THE GOVERNING
BODY OF COLLIER COUNTY AND AS EX-OFFICIO THE GOVERNING BOARD OF THE COLLIER
COUNTY WATER-SEWER DISTRICT, its successors and assigns (hereinafter referred to as
"County"). Mortgagee is used as singular or plural, as the context requires.
WITNESSETH:
WHEREAS, Mortgagee is the owner and holder of that certain UCC-1 Financing
Statement filed with the Secretary of State, Number 950000252883; Mortgage in favor of First
Union National Bank, N.A., as recorded in Official Records Book 2128, page 1637, and as
modified by instruments recorded in Official Records Book 2285, page 1534, Official Records
Book 2375, page 2385, Official Records Book 2462, page 1661, and Official Records Book
2631, Page 1356; and UCC-1 Financing Statement recorded in Official Records Book 2128,
page 1662; all of the Public Records of Collier County, Florida; (hereinafter referred to as
"Mortgage"), encumbering the premises legally described therein (hereinafter referred to as the
"Encumbered Property").
WHEREAS, County has requested and received from the fee simple owner of the
Encumbered Property non-exclusive easements for the installation and maintenance of utiliW
facilities over and across a portion of the encumbered premises legally described in Exhibit "A"
attached hereto and incorporated herein by virtue of reference, which premises are hereinafter
referred to as the "Easement Property."
WHEREAS, County has requested that Mortgagee consent to, join in and subordinate its
Mortgage to the interest that County has in the Easement Property to which request Mortgagee
has agreed.
NOW, THEREFORE, in consideration of Ten Dollars ($10.00), and other good and
valuable consideration, the receipt of which is hereby acknowledged, the Mortgagee does hereby
consent to, join in and subordinate the lien of its Mortgage to the grant of that certain easement
described herein over, under, and across the Easement Property and any interest of the County in
any utility facilities located therein or affixed thereto. Except as subordinated to the easement
OR: 2896 PG: 3097
described herein over, under, and across the Easement Property or any utility facilities located
therein or affixed thereto, said Mortgage shall remain otherwise in full force and effect.
IN WITNESS WHEREOF, the Mortgagee has caused these presents to be executed the
date and year first above written.
WITNESSES: FIRST UNION NATIONAL
BANK, a National Association
By:
PrintName: P_-.A.~L ~o'. l~Ret7T"
Title: v~Ge-- F N~-st tl~w'7-
STATE OF FLORIDA
COUNTY OF
The foregoing instrument was acknowledged before me this,~/~day of ~/~
2001, by~49r~t__ /¥, ~>/?-~ 77- ,as V/oz t~>f~t~,qT' of First Union Natior~l
Bank, a National Association. He/-~e is personally known to me
, · ~
(Seal)
.ary Public
grint Name:
My Commission Expires:
15891v1:06967.001
-2-
*** OR: 2896 PG: 3098 ***
EXHIBIT "A"
All of the area designated as "C.U.E." of the Plat of Carlton Lakes
Tract "3-A," as recorded in Plat Book 35, page 15, of the Public
Records of Collier County, Florida.
15891v1:06967.001
Prepared by and return to:
C. Perry Peeples, Esq.
Annis, Mitchell, Cockey, Edwards & Roehn
8889 Pelican Bay Blvd., Suite 300
Naples, Florida 34108
2861181 OR: 2896 PG: 3099
RECORDED in OPHCIAL RECORDS of COLLIER COUNTY, FL
09/24/2001 at 03:D~PM DWIGHT E, BROCK, CLERK
R~C ~ 15.00
Retn:
SHIRLEY NIX/ENGINEERING REVIEW
HORSESHOE DRIVE
HXT 5586
BILL OF SALE
This Bill of Sale evidencing the sale and conveyarF, e~f the water at3d sewer utility
facilities described herein is made this e;2.ff~, day o~"-'~'~ff."~~001, by NTC
DEVELOPMENT, INC., a Florida limited partn-~(-here~rfferre, d t~o ~.~"_S_eller")and the
Bo^m) OF COUNTY COMMISSIONERS OF COLLIER COUNTf, FL_,OffiD^, AS THE GOVERNrNG BODY
OF COLLIER COUNTY AND AS EX-OFFICIO THE GOVERN]~-BOARD OF THE COLLIER COUNTY
WATER-SEWER DISTRICT, its successors and assigns (hereinafter referred to as "Buyer").
WITNESSETH:
That said Seller, for and in consideration of the sum of Ten Dollars ($10.00), and other
good and valuable consideration, to said Seller in hand paid by the said Buyer, the receipt of
whereof is hereby acknowledged, has granted, bargained, sold, transferred, set over and
delivered, and by these presents does grant, bargain, sell, transfer, set over and deliver unto the
Buyer, and the Buyer's heirs, successors and assigns forever, all those certain water and sewer
utility facilities lying within the following described land, together with appurtenant easement
rights for the operation, installation and maintenance of said facilities, situate, lying and being in
Collier County, Florida, to wit:
See Exhibit "A" attached hereto and incorporated herein by reference.
The Seller, for itself and its successors, hereby covenants to and with the Buyer and its
successors and assigns that it is the lawful owner of the said goods and chattels herein referred to
as utility facilities; that said goods and chattels are free from all liens and encumbrances; that it
has good right, title and authority to sell same, and that it will warrant and defend the same
against the lawful claims and demands of all persons whomsoever. Seller and Buyer are used for
singular or plural, as the context requires.
OR: 2896 PG: 3100
IN WITNESS WHEREOF, Seller has caused these presents to be executed the date and
year first above written.
WITNESSES:
NTC DEVELOPMENT, LTD., a Florida
limited partnership
Print Na}n~: pa~r ,,,~
By: SW FLORIDA PARTNERS, INC., a
Florida corporation, General Partner
By: ~~~
Robert G. Claussen, President
(Corporate Seal)
STATE OF FLO,RID~ .
COUNTY OFC/"'~
The foregoing instrument was acknowledged before me this ~,7,~ day
2001, by Robert G. Claussen, as President, of SW Florida Partners, Inc., a Flo/fi'ff~}/corporaffon,
General Partner of NTC Development, Ltd., a Florida limited partnership, o(.~behalf of the
corporation and the partnership, who is personally known to me or produced
as identification.
(Seal)
My Commls ~..j~lres: C{[eryl Rclb¥
~'~'~;~ MY COMMISSION # CC695501 EXPIRES
~:~3~.'.'o--~ November 21 2001
>~ ~,~',~ BONDED THRU TI~OY FAIN INSURANCE, JNC
15888v I: 06967.0001
-2-
*** OR: 2896 PG: 3101 ***
EXHIBIT "A"
All of the area designated as "C.U.E." of the Plat of Carlton Lakes
Tract "3-A," as recorded in Plat Book 35, page 15, of the Public
Records of Collier County, Florida.
15891v1:06967.001
Prepared by and return to:
C. Perry Peeples, Esq.
Annis, Mitchell, Cockey, Edwards & Roehn
8889 Pelican Bay Blvd., Suite 300
Naples, Florida 34108
2861182 OR: 2896 PG: 3102
RECORDED in OFHCIAL RECORDS of COLLIER COUH?¥, ~L
09/24/2001 at 03:04PM DWIGHT E, BROCK, CLERK
REC ~BE
Retn:
SHIRLEY NIX/ENGINEERING REVIEW
HORSESHOE DRIVN
EXT 5585
DOC-,70
15,00
.70
UTILITY FACILITIES WARRANTY DEED
THIS INDENTURE, granted this ~/~ day ~ / ,2001, between
INC., a Florida limited pg.q~sh~ (hereinafter referred to as
Dy, xVELOPMENT,
Grantor ), and the BOARD OF COUNTY COMMISSIO~~z'COLLIERtJ~ COUNTY, FLORIDA, AS
THE GOVERNING BODY OF COLLIER COUNTY AND AS EX-OFFICIO THE GOVERNING BOARD OF
THE COLLIER COUNTY WATER-SEWER DISTRICT, its successors and assigns, (hereinafter
referred to as "Grantee").
WITNESSETH:
That said Grantor, for and in consideration of the sum of Ten Dollars ($10.00), and
other good and valuable consideration to said Grantor in hand paid by said Grantee, the
receipt whereof is hereby acknowledged, has granted, bargained and sold to the said Grantee,
and Grantee's heirs, successors and assigns forever, all water and sewer utility facilities lying
within the following described land, together with appurtenant easement rights for the
operation, installation and maintenance of said facilities, situate, lying and being in Collier
County, Florida, to-wit:
See attached Exhibit "A," which is incorporated herein by reference;
and said Grantor hereby fully warrants the title to said utility facilities and will defend the
same against the lawful claims of all persons whomsoever. For the purposes of this
conveyance, the utility facilities conveyed herein shall not be deemed to convey any of the
lands described in Exhibit "A." Grantor and Grantee are used for singular or plural, as
context requires.
OR: 2896 PG: 3103
IN WITNESS WHEREOF, the said Grantor has caused these presents to be executed
the day and year first above written.
WITNESSES:
NTC DEVELOPMENT, LTD., a Florida
limited partnership
By: SW FLORIDA PARTNERS, INC., a
Florida corporation, General Partner
Robert G. Claussen, President
(Corporate Seal)
STATE OF FJ~ ~/~. '_ ,.
COUNTY ~
The foregoing instrument was acknowledged before me this ,~..~ day
2001, by Robert G. Claussen, as President of SW Florida Partners, Inc., a Florisk~9~ration~s
Sole General Partner of NTC Development, Ltd., a Florida limited partnership{'w_~4 is pcrs0d/ally.
known to me or produced as id~ltification.
(Seal) ~v~iyn~od&~on~E~
15889vl: 06967.001
Chewl Raby
MY COMMISSION ,f CC693501 EXPIRES
November 21, 2001
BONDED THRU TI~OY FAIN INSURANCE, INC.
-2-
*** OR: 2896 PG: 3104 ***
EXHIBIT "A"
All of the area designated as "C.U.E." of the Plat of Carlton Lakes
Tract "3-A," as recorded in Plat Book 35, page 15, of the Public
Records of Collier County, Florida.
15891v1:06967.001
This instrument prepared by:
C. Perry Peeples, Esq.
Annis, Mitchell, Cockey, Edwards & Roehn
8889 Pelican Bay Blvd., Suite 300
Naples, Florida 34108
OWNER'S AFFIDAVIT
STATE OF/J~ ~.A
COUNTY~F~y~-~
On this ~ day o~ , 2001, before me personally appeared
ROBERT G. C~--~-SSEN,/~s President of ~ Florida Partners, Inc., a Florida corporation, as
Sole General Partner of N~.,D~VELOPMENT, LTD., a Florida limited partnership, owner of
property, to me personally known (hereinafter "Affiant"), who, being duly sworn on his oath, did
say that all of the persons, firms, and corporations, including the general contractor and all
subcontractors, who have furnished services, labor or materials according to plans and
specifications, or extra items, used in the construction or repair of water and sewer utility
facilities on the real estate hereinafter described, have been paid in full and that such work has
been fully completed and accepted by the owner.
Affiant further says that no claims have been made to the owner by, or is any suit now
pending on behalf of, any contractor, subcontractor, laborer or materialman, and further that no
chattel mortgages or conditional bills of sale have been given or are now outstanding as to the
subject utility facilities placed upon or installed in the aforesaid premises.
Affiant further says that the utility facilities described herein are encumbered by, or
subject to a UCC-1 Financing Statement filed with the Secretary of State, Number
950000252883; Mortgage in favor of First Union National Bank, N.A., recorded in Official
Records Book 2128, page 1637; as modified in Official Records Book 2285, page 1534, Official
Records Book 2375, page 2385, Official Records Book 2462, Page 1661, and Official Records
Book 2631, page 1356; and UCC-1 Financing Statement recorded in Official Records Book
2128, page 1662; all of the Public Records of Collier County, Florida;
Affiant, as and on behalf of the owner of the subject utility facilities, does for valuable
consideration hereby agree and guarantee to hold the Board of County Commissioners of Collier
County, Florida as the governing body of Collier County and as Ex-Officio the Governing Board
of the Collier County Water-Sewer District, harmless against any lien, claim or suit by any
general contractor, subcontractor, mechanic or materialman, and against chattel mortgages,
security interests or repair of the subject utility facilities. Affiant is used as singular or plural, as
the context requires.
The utility facilities referred to herein are located within the real property described in the
attached Exhibit "A."
NTC DEVELOPMENT, LTD., a Florida
limited partnership
By: SW FLORIDA PARTNERS, INC., a
Florida corporation, General Partner
Robert G. Claussen, President
(Corporate Seal)
STATE OF FLO~"~.~,/7.. .'
COUNTY OF
The foregoing Owner's Affidavit was sworn to and subscribed before me by Robert G.
Claussen, as President of SW Florida Partners, Inc., a Florida corporation, General Parmer of
NTC Development, Ltd., a Florida limited partnership, on behalf of the corporation and the
parmership, who is personally known to me or produced
as identification.
(Seal)
WITNESS my hand and official seal this ~ day of ~~.~_o4.J.~", 2001.
~otar~ Pub~ - ~-- ~
Printed Name: t3~ m'tat~/'
My Commission Expires: I
15886v1:06967.001
.,,,;..:... g%.,~;~ ,~, Cheryl Raby
.~.:;"~I~'~:.~ MYCOMMISSION# CC693501 EXPIRES
~#,.~ November 21, 2001
-2-
EXHIBIT "A"
All of the area designated as "C.U.E." of the Plat of Carlton Lakes
Tract "3-A," as recorded in Plat Book 35, page 15, of the Public
Records of Collier County, Florida.
I~csted ~n flies in
15891v1:06967.001
This instrument prepared by:
C. Perry Peeples, Esq.
Garlick, Stetler & Peeples, LLP
8889 Pelican Bay Blvd., Suite 300
Naples, Florida 34108
(941) 59%7088
ATTORNEY'S AFFIDAVIT
STATE OF FLORIDA )
COUNTY OF COLLIER )
On this /t--/~day of {~/10, t'~ , 2001, before me personally appeared
C. Perry Peeples, a licensed attorney authorized to practice in the State of Florida, to me
personally known, whose current business address and telephone number are Garlick, Stetler &
Peeples, LLP, 8889 Pelican Bay Blvd., Suite 300, Naples, Florida 34108, (941) 597-7088
(hereinafter "Affiant") who, being duly sworn on his oath, does say:
1. This Affidavit is given as an inducement to the Board of County Commissioners
of Collier County, Florida, as the governing body of Collier County and as Ex-Officio the
Governing Board of the Collier County Water-Sewer District, to accept the dedication or
conveyance of water and sewer utility facilities located within or upon the real property
described in the attached Exhibit "A," which is incorporated herein by reference, said land being
located in Collier County, Florida.
2. The Affiant has examined record title information to both the real and personal
property referenced in this Affidavit, including but not limited to, information requested from the
Florida Secretary of State relative to any Uniform Commercial Code financing statements.
3. The record owner of the real and personal property described herein is NTC
Development, Ltd., a Florida limited partnership (hereinafter "Owner"). The Owner acquired
record title to the subject real property by instrument recorded at Official Records Book 2106,
page 321, Public Records, Collier County, Florida (copy attached).
4. Affiant has examined-partnership and corporate information obtained from the
Secretary of State. The Owner is current and active within said state, and is currently authorized
to do business in the State of Florida. Robert G. Claussen, as President of SW Florida Partners,
Inc., a Florida corporation, as Sole General Partner of NTC Development, Ltd., a Florida limited
partnership, is authorized to execute the instruments on behalf of the partnership in conjunction
with the conveyance of the subject real and personal property.
5. The subject real and personal property is encumbered of record, or is the subject
of financing statements filed in the Public Records of Collier County, Florida, or the Office of
the Secretary of State as follows: UCC-1 Financing Statement filed with the Secretary of State,
Number 950000252883; Mortgage in favor of First Union National Bank, N.A. recorded in
Official Records Book 2128, page 1637; as modified by instruments recorded in Official Records
Book 2285, Page 1534, Official Records Book 2375, Page 2385, Official Records Book 2462,
page 1661, and Official Records Book 2631, page 1356; and UCC-1 Financing Statement
recorded in Official Records Book 2128, Page 1662; all of the Public Records of Collier County,
Florida.
o
Affiant further states that the information contained in this Affidavit is true,
correct and current as of the date this Affidavit is,~given.
C. PERRY/PEEPLES
STATE OF FLORIDA
COUNTY OF COLLIER
The foregoing Attorney's Affidavit was sworn to and subscribed before me by C. Perry
Peeples, who is personally known to me.
WITNESS my hand and official seal this Iq H4day of /T/('~_f(~!h ,2001.
(Seal)
Notary Public/ ' - '
Printed Name:
My Commission Expires:
NSClients\NTC Der LTD_0204~Attomey's Affidavit-Carlton Lakes. DOC
-2-
EXHIBIT "A"
All of the area designated as "C.U.E." of the Plat of Carlton Lakes
Tract "3-A," as recorded in Plat Book 35, page 15, of the Public
Records of Collier County, Florida.
COLLIER COUNTY GOVERNMENT
COMMUNITY DEVF, I,OPMENT AND ENVIRONMENTAL SERVICES DIVISION
ENGINEERING REVIEW SECTION
PLANNING SERVICES DEPARTMENT
2800 NORTH HORSESHOE DRIVE
NAPLES, FL 34104
June 19, 2001
Mr. Jim Carr, P.E.
Agnoli, Barber & Brundage, Inc.
7400 Tamiami Trail North
Naples, FL. 34108
Re: Carlton Lakes Unit 3-A
Dear Mr. Carr:
This is to inform you that the above referenced project has been
granted preliminary approval by Engineering Review in compliance
with Collier County Land Development Code, Section 3.2.6.5.2.
All water and sewer facilities approved and accepted and required
to be maintained by Collier County shall be conveyed to the
County pursuant to the provisions set forth in Collier County
Ordinance No. 97-17, as amended.
You are reminded that it is your responsibility to petition the
Development Services Director for final approval of the
improvements upon the expiration of the minimum one (1) year
maintenance period. After satisfactory completion of all final
inspections, the Board of County Commissioners shall adopt a
resolution giving final approval of the required improvements,
acknowledging the dedication(s) of the final subdivision plat and
establishing County responsibility for maintenance of the
required improvements if it is the Board's desire to accept and
maintain the facilities.
If you should have any questions or if we may be of assistance,
please advise.
Very truly yours,
John R. Houldsworth
Senior Engineer
cc: Daryl Hughes, Engineer II
Shirley Nix, Engineering Technician
PHONE ~ 941 ) 403-2400 FAX (941 ) 643-6968 www. co.collier, fl.us
COLLIER COUNTY GOVERNMENT
COMMUNITY DEVELOPMENT AND ENVIRONMENTAL SERVICES DIVISION
ENGINEERING REVIEW SECTION
June 21, 2001
June Miller
Agnoli, Barber & Brundage, Inc.
7400 Tamiami Trail N., #200
Naples, FL 34108
Re: Carlton Lakes, Unit 3-A
PLANNING SERVICES DEPARTMENT
2800 NORTH HORSESHOE DRIVE
NAPLES, FL 34104
Dear Mr. Carr:
This is to inform you that the above referenced project has been granted preliminary approval by
Engineering Review in compliance with Collier County Land Development Code, Section 3.
All water and/or sewer facilities approved, accepted and required to be maintained by Collier
County shall be conveyed to the County pursuant to the provisions set forth in Collier County
Ordinance No. 97-17, as amended.
You are reminded that it is your responsibility to petition the Development Services Director for
final approval of the improvements upon the expiration of the minimum one (1) year
maintenance period. After satisfactory completion of all final inspections., the Board of County
Commissioners shall grant final approval of the required improvements establishing County
responsibility for maintenance of the required improvements if it is the Board's desire to accept
and maintain the facilities.
If you should have any questions or if we may be of assistance, please advise.
Very truly yours,
Engineering Technician II
CC:
Joe Cheatham, Wastewater Director
Paul Mattausch, Water Director
Lisa Taylor, Public Works
John Houldsworth, Engineering Review
June Miller, ABB
PHONE (941) 403-2400 FAX (941) 643-6968 www. co.collier, fl.us
Illlll~
lmmml,~, l~lXlUl~l
mmmmmkT~
IIIIII!.~ ·
IIIIIII61'~
IIIIIII1-~. ~ ~
lmmmmmmmJ..)~u r~ k)tk~,J~, ~c.
ENGINEER'S FINAL PAYMENT CONFIRMATION
The undersigned engineer of record of the project known as Carlton Lakes 3A hereby confirms
that the firm of Agnoli, Barber & Brundage, Inc. has been paid in full by NTC Development Ltd.
for labor, services or materials furnished in the design, permitting, and construction of the water
and sewer utility facilities within this project. This confirmation of payment is not a release for
any future right to claim a lien for work performed in connection with the property.
James A. Ca_rr, P.E.
Printed Name
STATE OF FLORIDA
COUNTY OF COLLIER
On this ~?h day of ~'g'~e. tY~,~)t ,2001, personally James A. Carr, whom I
know personally and acknowledged that he executed the same.
1-764j 1 .cert
Public
Printed Name: June A. Miller
lllllk~
Ii1111
Illlllk'l'~
i!111111'~
PRESSURE TEST REPORT
PROJECT Carlton Lakes Tract 3A, PN 6696-3A/X002
DATE 1/23/01
WITNESSED BY Jim Bailey / Randy Casey
TYPE OF LINE:
FORCEMAIN X POTABLE IRRIGATION FIRE
DIAMETER 8 INCHES, D
LENGTH 1875 FEET, S
TEST PRESSURE 150 PSI
TEST:
START 157 PSI ~
10:00 a.m.
STOP 157 PSI ~ 12:00 noon
AMOUNT USED Zero GAL
AVERAGE PSI 157
ALLOWABLE LEAKAGE:
L = SD>P/133,200 GAL/HR
= 1.38 GAL/HR
X2= 2.76 GAL/2HR
PASSED Yes
~~ Department of
'"" I P ti
Environmenta rotec on
~~~--~_--2:-::-2~:~- Sou~ District
Jeb Bush P.O. Box 2549
Governor Fo~ Hyers, Florida 33902-2549
March 8, 2001
David B. Struhs
200~Secretary
REC£~v£D
Robert G. Claussen, Managing Parmer
NTC Development Limited
6025 Carlton Lakes Blvd.
Naples, FL 34110
Re:
Collier County - PW...
Carlton Lakes Unit 3A Water
Distribution System
(Collier County Regional WTP)
145371-004-DS
Southwest Coast EMA
Dear Mr. Claussen:
This acknowledges receipt of certification that the subject water distribution system extension has
been completed in accordance with the plans and related materials permitted by this agency under
Permit Number 145371-004-DS dated October 27, 2000.
Based on this certification and satisfactory bacteriological results, we are approving these
facilities for service. Your continued cooperation in our water supply program is appreciated.
Sinc.erely,
O. James Oni
Professional Engineer
Water Facilities
OJO/MFJ/klm
cc: James A. Carr, P.E.
Thomas E. Kuck, P.E.
"More Protecdon, Less Process"
Printed on recycled paper.
Florida Department of Environmental ~Y
Twin Towers Office Bldg., 2600 Blair Stone Road, TallahaSSee, Florida 3~-~2~00
* ' '~'Ot~_
DOMESTIC WASTEWATER COLLECTION/TRANSMISSION SYS"I'E'~,~,
CERTIFICATION OF COMPLETION OF CONSTRUCTION
INSTRUCrIONS: This form is to be completed and submitted to the Department, prior to placing the system into operation. A
collection/transmission system should not be placed into operation without prior Department approval. All information is to be
typed or printed in ink and all blanks must be filled.
Construction Permit No.: 50581
Dated: 10/06/00
Name of Project: CARLTON LAKES UNIT 3A
Name of Owner: NTC DEVELOP[IENT L£MITED
Name of design engineer and Florida registration number (if different from the engineer signing certification):
SAME
Date(s) connection to existing system or treatment plant:
Treatment plant serving project
Name: NORTH COUNTY REGIONAL WATER RECLAMATION FACILITY
County: COLLIER
DEP Identification Number (also known as WAFR or GMS
Substantial deviations from the approved plans and specifications
NONE
City: NAPLES
Number): FLA 01.~139
if required):
DEP Form 62-604.300(7Xb)
Fl[cc'live June 1,1992
Page 1 of 3
WAIVER OF LIEN
KNOW ALL MEN BY THESE PRESENTS~ that Timothy C. Mitchell, Sr., as President,
of Haleakala Construction. Inc. for and in consideration of ONE HUNDRED FOURTYTWO
THOUSAND FIVE HUNDRED SEVENTYFIVE DOLLARS and FIFTY CENTS ( $142,575.50 ) and
other good and valuable considerations, lawful money of the United States of America, to me in hand
paid, the reciept whereof is hereby acknowledged, does hereby waive, release, remiss, and relinquish any
and all right to claim any lien or liens for work performed or material furnished, or any kind or class of
lein whatsoever on the following described property.:
( Please provide full name and location of development and a description of the utility system constructed )
All the Potable Water and Sanitary Sewer system for Carlton Lakes Unit 3-A as depicted on the
construction drawings prepared by Agnoli Barber and Brundage Engineers.
By'
Haleakala Construction, Inc.
5758 Taylor Road
.tclOrida 34109-1856
hell, Sr., President
STATE OF FLORIDA )
)
COUNTY OF COLLIER )
SS:
The foregoing instrument was signed and acknowledged before me this 22 nd day of January, 2001
.... rsonally known to me and who did not take an oath.
B~enda K Mercham
CC 732239
7/1/96 11-3
State of Florida
Department of #ea[th
Office of Laboratory Services
Jacksonville, Miami, Pensacola
Tan~a, West PaLm Beach
DRINKING WATER
BACTERIOLOGICAL ANALYSIS
Press hard, (5) copies
FOR LAB USE ONLY
SYSTEM NAME: SYSTEM I.D. NO:
ADDRESS: COUNTY:
COLLECTOR:
SAMPLE SITE (Locality or Subdivision):
DATE AND TIME COLLECTED: ._ .:; .
TYPE OF SUPPLY(Circle one): Community water system~ Noncommunity water system
Private well SWin~ing pool Bottled water
SYSTEM PHONE #:
DISTRICT:
COLLECTOR PHONE #:
Nontransient - noncommunity water system
Limited Use system
TYPE OF SAMPLE(Circle one):
Compliance
(Check Box)
[ ] Distribution
[ ] Raw
Repeat Replacement Main clearance
TO BE COMPLETED BY COLLECTOR OF SAMPLE
COLL.
NO.
SAMPLE POINT
(Specific Address)
* Results in :his column are presumptive.
P - Coliforms are present
A - Coliforms are absent
Cl
RES'D pH
Well survey Other
[ ] Check here if payment made
to county public health unit
TO BE COMPLETED BY LAB
ANALYSIS METHOD: MF MTF MMO-MUG PA
*TOTAL
NON
COLIFORM
Total coliform and fecal coliform or E. coli
C - Confluent growth
TNTC - Too numerous to count
CONFIRM
TOTAL
CONFIRM
FECAL E. COLI
SAMPLE NUMBER
:onfirmation will follow in 24-48 hours.
TA - Turbid, Absence of gas or acid
INVOICE ADDRESS (if different than address below):
INTERPRETATIONS-REMARKS BY. PROGRAM REVIEWER
NAME AND MAILING ADDRESS OF PERSON/FIRM TO RECEIVE REPORT
REVIEWING OFFICIAL:
TITLE:
SATISFACTORY
INCOMPLETE COLLECTION INFORMATION
REPEAT SAMPLES
REPLACEMENT SAMPLES
State of FLorida
Department of Health
Office of Laboratory Services
Jacksonvi[[e, #iami, Pensacola
Tampa, Uest PaLm Beach
DRINKING WATER
BACTERIOLOGICAL ANALYSIS
FOR LAB USE ONLY
Press hard, (5) copies
SYSTEM NAME:
ADDRESS:
COLLECTOR:
SAMPLE SITE (Locality or Subdivision):
DATE AND TIME COLLECTED:
TYPE OF SUPPLY(Circle one):
TYPE OF SAMPLE(Circle one):
SYSTEM I.D. NO:
COUNTY:
SYSTEM PHONE #:
DISTRICT:
COLLECTOR PHONE #:
Community water system Noncommunity water system Nontransient - nonco~munity water system
Private well Swimming pool Bottled water Limited Use system
Compliance Repeat Replacement Main clearance Well survey Other
(Check Box)
[ ] Distribution [ ] Check hero if payment made
[ ] Raw to county public health unit
TO BE COMPLETED BY COLLECTOR OF SAMPLE T,D BE COMPLETED BY LAB
ANALYSIS METHOD: ME MTF__ MMDz,,MUG PA
COLL. SAMPLE POINT C[ NON CONFIRM CONFIRM
NO. (Specific Address) RES'D pH COLIFORM *TOTAL TOTAL FECAL E. COLI SAMPLE NUMBER
* Results in this column are presumptive. Total coliform and fecal coliform or E. coti :onfirmation will follow in 24-48 hours.
P - Coliforms are present C - Confluent growth TA - Turbid, Absence of gas or acid
A - Co[iforms are absent TNTC - Too numerous to count
INVOICE ADDRESS (if different than address below):
INTERPRETATIONS-REMARKS BY. PROGRAM REV[EWER
NAME AND MAILING ADDRESS OF PERSON/FIRM TO RECEIVE REPORT
REVIEWING OFFICIAL:
TITLE:
( )
( ) SATISFACTORY
( ) INCOMPLETE COLLECTION INFORMATION
( ) REPEAT SAMPLES
( ) REPLACEMENT SAMPLES
State of Ftorida
Department of Hearth
Office of Laboratory Services
Jacksonville, Miami, Pensacola
Tampa, West Palm Beach
DRINKING WATER
BACTERIOLOGICAL ANALYSIS
:FOR LAB USE ONLY
Press hard, (5) copies
SYSTEM NAME:
ADDRESS:
COLLECTOR: :
SAMPLE SITE (Locality or Subdivision):
DATE AND TIME COLLECTED:
TYPE OF SUPPLY(Circle one):
TYPE OF SAMPLE(Circle one):
SYSTEM I.D. NO:
COUNTY:
SYSTEM PHONE #:
DISTRICT:
COLLECTOR PHONE #:
Co,unity water system Noncommunity water system Nontransient - noncommunity water system
Private well Swir~ning pool Bottled water Limited Use system
Compliance
(Check Box)
[ ] Distribution
[ ] Raw
Repeat Replacement Main clearance
Well survey Other
[ ] Check here if payment made
to county public health unit
TO BE COMPLETED BY COLLECTOR OF SAMPLE TO BE COMPLETED~.QY LAB _
ANALYSIS METHOD: MF MTF MMO-MUG PA
COLL. SAMPLE POINT Cl NON CONFIRM CONFIRM
NO. (Specific Address) RES'D pH COLIFORM *TOTAL TOTAL FECAL E. COLI SAMPLE NUMBER
* Results in this column are presumptive. Total coliform and fecal coliform or E_= ~oli :onfirmation will follow in 24-48 hours.
p - Coliforms are present C - Confluent growth TA - Turbid, Absence of gas or acid
A - Coliforms are absent TNTC - Too numerous to count
INVOICE ADDRESS (if different than address below): INTERPRETATIONS-REMARKS BY. PROGRAM REVIEWER
NAME AND MAILING ADDRESS OF PERSON/FIRM TO RECEIVE REPORT
REVIEWING OFFICIAL:
TITLE:
( )
( ) SATISFACTORY
( ) INCOMPLETE COLLECTION INFORMATION
( ) REPEAT SAMPLES
( ) REPLACEMENT SAMPLES
State of Florida
Department of Health
Office of LaDoratocy Services
Jack$~vit~e, Ni~mi, Pensacola
T~ West Palm Beach
DRINKING WATER
BACTERIOLOGICAL ANALYSIS
FOR LAB USE ONLY
SYSTEM NAME:
ADDRESS:
COLLECTOR:
Press hard, (5) copies
SYSTEM I.D. NO:
COUNTY:
SYSTEM PHONE #:
DISTRICT:
SAMPLE SITE (Locality or Subdivision):
COLLECTOR PHONE #:
DATE AND TIME COLLECTED:
TYPE OF SUPPLY(Circle one):
TYPE OF SAMPLE(Circle one):
Community water system Noncommunity water system Nontransient - noncommunity water system
Private well Swimming pool Bottled water Limited Use system
Compliance Repeat Replacement Main clearance Well survey Other
(Check Box)
[ ] Distribution [ ] Check here if payment made
[ ] Raw to county public health unit
TO BE COMPLETED BY COLLECTOR OF SAMPLE TO BE COMPLETED BY LAB
ANALYSIS METHOD: MF~ MTF MMO-MUG PA
COLL. SAMPLE POINT CI NON CONFIRM CONFIRM
NO. (Specific Address) RES'D pH COLIFORM *TOTAL TOTAL FECAL E. COLI SAMPLE NUMBER
* Results in this column are presumptive.
P - Co[iforms are present
A - Coliforms are absent
Total coliform and fecal coliform or E. call confirmation will follow in 24-48 hours.
C - Confluent growth TA - Turbid, Absence of gas or acid
TNTC - Too numerous to count
INVOICE ADDRESS (if different than address below):
INTERPRETATIONS-REMARKS BY. PROGRAM REV%EWER
NAME AND MAILING ADDRESS OF PERSON/FIRM TO RECEIVE REPORT
REVIEWING OFFICIAL:
TITLE:
( )
( ) SATISFACTORY
( ) INCOMPLETE COLLECTION INFORMATION
( ) REPEAT SAMPLES
( ) REPLACEMENT SAMPLES
CERTIFICATION OF CONTRIBUTORY ASSETS
PROJECT NAME
LOCATION:
CARLTON LAKES UNIT 3-A
CARLTON LAKES SUBDMSION
NAME AND ADDRESS OF OWNER:
NTC DEVELOPMENT
2405 PIPER BLVD.
NAPLES. FLORIDA 34110
TYPE UTILITY SYSTEM:
POTABLE WATER SYSTEM
DESCRIPTION AND COST OF MATERIAL. LABOR. AND SERVICES
POTABLE WATER
ASHWOOD LANE
CONNECT TO EXISTING 6" WATER
8" PVC DR-18 WATER
8" GATE VALVE
FIRE HYDRANT
3" WATER SLEEVE
4" PVC CONDUIT
FITTINGS
CHLORINATE & TEST
ELECTRONIC LOCATORS
MANCHESTER PLACE
3" WATER SLEEVE
Sub Total
2 EA $1,000.00 $2,000.00
1900 LF $13.90 $26,410.00
I EA $800.00 $800.00
3 EA $2,100.00 $6,300.00
450 LF $5.70 $2,565.00
360 LF $6.00 $2,160.00
I LS $6,100.00 $6,100.00
I EA $1,000.00 $1,000.00
22 EA $20.00 $440.00
640 LF $5.70 $3,648.00
$51,423.00
(If more space is reqmred, use additional page(s). Number each page and include the name of the project.
7/1/96 11-5
CERTll*ICATION OF CONTRIBUTORY ASSETS
PROJECT NAME
LOCATION:
CARLTON LAKES UNIT 3-A
CARLTON LAKES SUBDIVISION
NAME AND ADDRESS OF OWNER:
NTC DEVELOPMENT
2405 PIPER BLVD.
NAPLES. FLORIDA 34110
TYPE UTILITY SYSTEM:
SANITARY SEWER SYSTEM
DESCRIPTION AND COST OF MATERIAL, LABOR. AND SERVICES
SANITARY SEWER
ASHWOOD LANE
CONNECT TO EXISTING 8" SEWER
8"PVC SDR-26 SEWER 0-6'CUT
8" PVC SDR-26 SEWER 6-8' CU']'
4'DIA MANHOLE 0-6'CUT
4'DIA MANHOLE 6-8'CUT
6" PVC LATERAL
6" SINGLE CLEAN-OUT
6" DOUBLE CLEAN-OUT
T.V. VIDEO SEWER
MANCHESTER PLACE
CONNECT TO EXISTING 8" SEWER
8" PVC SDR-26 SEWER 0-6' CUT
4'DIA MANHOLE 0-6'CUT
6" PVC LATERAL
6" SINGLE CLEAN-OUT
6" DOUBLE CLEAN-OUT
T.V. VIDEO SEWER
Sub Total
2 EA $1,500.00 $3,000.00
1219 LF $22.00 $26,818.00
310 LF $26.00 $8,060.00
6 EA $1,400.00 $8,400.00
1 EA $1,750.00 $1,750.00
740 LF $10.50 $7,770.00
2 EA $200.00 $400.00
19 EA $225.00 $4,275.00
1 EA $2,050.00 $2,050.00
1 EA $1,500.00 $1,500.00
546 LF $22.00 $12,012.00
3 EA $1,450.00 $4,350.00
585 LF $10.50 $6,142.50
2 EA $200.00 $400.00
i 3 EA $225.00 $2,925.00
i EA $1,300.00 $1,300.00
$91,152.50
(If more space is required, use additional page(s). Number each page and include the name of the project.
7/1/96 I1 -5
mmmmF~ lb~U~l
mmmmm&n
mmmmmm
mmmmm).~AELBER&
mmmlmmk'l-~
iliiIi1~ .....
lmmmmmf. J_;~U~U~u~,XN~.
January29,2001
Collier County Board of Commissioners
3301 Tamiami Trail East
Naples, FL 34112
Re: Carlton Lakes Unit 3A
Honorable Commissioners:
The purpose of this letter is to certify that to the best of my knowledge, information and belief
and in accordance with commonly accepted procedures consistent with applicable standards of
practice, the water and sewer facilities to be dedicated at the above-referenced project have
been constructed within Tract R of the plat of Carlton Lakes Unit No. 3A, as recorded in Plat
Book 35, pages 16 - 18 of the Public Records of Collier County, Florida. This is not a guaranty
or warranty, either expressed or implied.
Sincerely,
James A. Carr, P.E.
JAC/jam
1-765j l.,2erl
WARRANTY
The undersigned parties do hereby warrant and/or guaranty all work executed by the contractor
on the water and/or sewer ~stems of (Developer) CARLTON LAKES UNIT 3-A to be free from
defects in material and workmanship for a period of at least one ( I ) year from the date of acceptance by
the Collier County Board of County Commissioners. The undersigned parties further agree that they will,
at their own expense, repair and replace all such defective work and all other work damaged by said
defective work under this Warranty - Guaranty.
It is furthermore understood that the consideration for the giving of this Warranty and/or
Guaranty is the requirement by the General Conditions and Specifications under which the contract was
let that such Warranty and/or Guaranty would be given.
Haleakala Construction, Inc.
STATE OF FLORIDA )
)
COUNTY OF COLLIER )
SS:
The foregoing instrument was signed and acknowledged before me this _22 nd day of January, 2001
by Timothy C. Mitchell, St, who is personally known to me and who did not take an oath.
CC 732239
7/1/96 11-2
Official Receipt - Collier County Board of County Commissioners
CDPR1103 - Official Receipt
Trans Number
252056
Date Post Date
03113/2001 12:26:17 PM 03/13/2001
Payment Slip Nbr
UT 82861
HALEAKALA CONSTRUCTION, INC.
HIGHWOOD PARK LN/CARLTON LAKES UNIT 3 A
Payor · HALEAKALA CONSTRUCTION
Fee Code
42CYIN
Fee Information
Description
COUNTY INVOICES
GL Account
40800000011510000000
Total
Amount
$277.88
$277.88
Waived
Payments
Payment Code Account/Check Number Amount
CHECK 027892 $277.88
Memo:
DOR1380, W/O ~034204/032603,
+ BACT
Total Cash / $0.00
Total Non-Cash ~ $277.88
Total Paid L $277.88
Cashier/location: CROMEENES_A / 3
User: AVILES_L
Collier County Board of County Commissioners
CD-Plus for Windows 95/NT
Printed:09/13/2001 11:58:41 AM
May-Il-01 ~:~.PM~, Inc. of Naples 435-9082 P.02
FIRE PREVENTION BUREAU
1780 Irnmokalee Road · Naples, Florida 34110
(941 ) 597-9227 · Fax (941) 597-3522
May 11, 2001
PMS
2335 9th St. N., Suite/I.408
Naples, FL 34103
RE: Hydrant Flow for Carlton Lakes- 6254, 6219, 6171 Ashwood Lane
Dear Sir,
The North Naples Fire Control and Rescue District has conducted a flow test at the
above location. This also will serve as an invoice of $3500 to cover the cost of the test
Please make your check payable to North Naples Fire Department, and you must
reference the name of the job on the check.
Following are the results of the flow test:
Static: 70 Resid: 38
Flow: 787 Pitot: 22
If you have any questions, please do not hesitate to give me a call at 597-9227.
SinTrely,
Karl K. Reynolds, Fire Marshal
Norlh Naples Fire Prevention Bureau
KKR/dw
I"l'~)li2hhi(~llJ.] ¢ll~iltc',.'{"-,, 1',]31111¢1"-,. '~tl{", CV(>I'h ~-~
SDP-2001 -A R-683
JaSmine Pointe
Project # · 2001030064
Date. '1/17/01
GRAVITY SEWER
INFILTRATION TEST REPORT
PROJECT
Carlton Lakes 3-A Manchester Place
PN 6696-3A TN X002
WITNESSED BY Jim Bailey
PROCEDURE:
TIME DATE
MEASUREMENT 10:30 a.m. 3/27/01 N/A
MEASUREMENT 10:30 a.m. 3/28/01 N/A
INFILTRATION Zero GPD
VERTICAL DISTANCE
LID TO WATER
Line was plugged at existing SMH.
ALLOWABLE LEAKAGE:
SEWER SIZE 8
INCHES, D
TOTAL LENGTH 555
FT/5280 = 0.10 MI, L
ALLOWABLE LEAKAGE 50 GPD/MI/INCH DIA
AL = (50XDXL) = 40
GPD
PASSED Yes
APR 0 2 2001
l.cc'(;OtllltV: 1(>23 {Icu,h" $~. ,~,~lil~' II)1 t',,~ ,\l\,.'t".,1 h,tid.~ ?,.:;'>(> <141 ~S4 117S t:,kX: ',94l)334 1175
GRAVITY SEWER
INFILTRATION TEST REPORT
PROJECT
Carlton Lakes 3-A Ashwood Lane
PN 6696-3A TN X002
WITNESSED BY Jim Bailey
PROCEDURE:
TIME DATE
MEASUREMENT 10:45 a.m. 3/27/01 N/A
MEASUREMENT 10:45 a.m. 3/28/01 N/A
INFILTRATION Zero GPD
VERTICAL DISTANCE
LID TO WATER
Line was plugged at existing SMH.
ALLOWABLE LEAKAGE:
SEWER SIZE 8
INCHES, D
TOTAL LENGTH 740
FT/5280 = 0.14 MI, L
ALLOWABLE LEAKAGE 50 GPD/MI/INCH DIA
AL = (50XDXL) = 56 GPD
PASSED Yes
APR 0 2 200'i
,,,m.,mmy,,~
lmmmm~/.~ ,~ ~,~ T
I
IIIII1~ T~ o
Illlllk'l'~
mmmmmml.J..Jt~u IN LJJ¥,~J~, inc.
SDP'2001-AR.683
Jasmine Poir~te
Project ~7 · 2001030064
Date · 4/17/01
GRAVITY SEWER
INFILTRATION TEST REPORT
PROJECT
Carlton Lakes 3-A Ashwood Lane
PN 6696-3A TN X002
WITNESSED BY Jim Bailey
PROCEDURE:
TIME DATE
MEASUREMENT 10:50 a.m. 3/27/01 N/A
MEASUREMENT 10: 50 a.m. 3/28/01 N/A
INFILTRATION Zero GPD
VERTICAL DISTANCE
LID TO WATER
ALLOWABLE LEAKAGE:
SEWER SIZE 8
INCHES, D
TOTAL LENGTH 800
FT/5280 = 0.15 MI, L
ALLOWABLE LEAKAGE 50 GPD/MI/INCH DIA
AL = (50XDXL) = 60
GPD
PASSED Yes
James A. Cart, P.E.#51318
APR 0 2 2001
Main ¢)fticc: 740{! ['..l~i..!li'll'aiIN,~4.ilc20(L N:?Ics. t'!,,li~i;3tl<~l c941 597 3111 FAX: 941)566-2203
?~5 P02 $~N 25 ~01 16:5~
9~19976645.~INTS&COATINGS
"Tke
Rehabi~itadon!
To ~om ~t M~'¥ Concertt: supplied tO,~n the
ZO0. 3n ac~ptable bituminotss or
se:tier.
C;ari A. Laquidar~
p~sident /
COLLIER COUNTY UTILITIES
WASTEWATER DEPARTMENT
PROJECT VIDEO REVIEW
DATE OF REVIEW:
PROJECT NAME:
ENGINEER OF RECORD:
3/9/2001
Carlton Lakes Tract 3A County (North)
CONSTRUCTION CONTRACTOR: Haleakala
VIDEO CONTRACTOR: Sewer Viewer
COMMENTS: Lines and services acceptable
RECOMMENDATIONS:
ACCEPTABLE:
REVIEW NUMBERED COMMENTS IN ONE YEAR:
NUMBERED COMMENTS UNACCEPTABLE: (REPAIR/REPLACE):
OTHER RECOMMENDATIONS:
Signature:
David Fitts
COLLIER COUNTY GOVERNMENT
COMMUNITY DEVELOPMENT AND ENVIRONMENTAL SERVICES DIVISION
ENGINEERING REVIEW SECTION
April 2, 2001
PLANNING SERVICES DEPARTMENT
2800 NORTH HORSESHOE DRIVE
NAPLES, FL 34104
Mr. Jim Carr
Agnoli, Barber & Brundage, Inc.
7400 Tamiami Trail N. Suite 200
Naples, Florida 34108
941-597-3111
RE: Carlton Lakes 3-A, Water & Sewer
Dear Mr. Carr:
A preliminary inspection of the referenced project was conducted by Randy Casey of
the Engineering Review Section of the Planning Services Department on April 2, 2001.
Conditions were found to be acceptable, and appear to meet County standards.
If you should have any questions, please do not hesitate to call Randy Casey at (941)
403-2418.
Sincerely' ,~z~//
Randy Casey
Engineering Inspector
cc:
Lisa Taylor, Engineering Technician, Public Works
Joe Cheatham, Wastewater Director, Utilities
Paul Mattausch, Water Director, Utilities
Diane Deoss, D.O.R. Billing Supervisor
Don Nobles, Engineering Inspections Supervisor
Randy Casey, Engineering Inspector
Shirley Nix, Engineering Tech. II, Engineering Review Section
File