Cedar Hammock ClubhouseMEMORANDUM
DATE: February 26, 2000
TO: Maureen Kenyon, Supervisor, Clerk to Board
FROM: Shirley Nix, Engineering Technician II /
Project Plan Review
RE: Cedar Hammock Clubhouse
Water and/or Sewer Facilities Acceptance
Recording Fee Number 113-138312-649030
On /~/ /~ , /-99~The Board of County Commissioners
grant~d/final acceptance of ~he water and/or sewer facilities
within the above-referenced project·
Attached, please find the following recorded, in order:
1. Bill of Sale
'2. Utilities Facilities Warranty Deed
Also, please find attached the following documents for your
files·
Copy of preliminary approval letter from Engineering
Review
Copy of Letter of Credit accepted for maintenance
Engineer's final payment confirmation
Certification of pressure testing of water lines by
Engineer of Record
Bacteriological clearances (DER certification) for
water facilities
DER Placement-in-Service letter for sewer facilities
Contractor'S Final Release of Lien
Lab results on bacteriological test for water lines
Memorandum to Maureen Kenyon, Supervisor, Clerk to Board
February 26, 2000
Page Two
11.
Verification of final cost (Detailed: quantities,
sizes, unit cost, total cost, etc.)
12.
Letter by Engineer certifying that all water and/or
sewer facilities are located within the public
right-of-way or dedicated easements
13.
Contractual Guarantee for material and workmanship for
a period of at least one year after the Board of County
Commissioners' acceptance for both water and sewer
facilities
14.
Payment of water usage, laboratory and administrative
charges for filling, flushing and bacteriologically
certifying water lines from invoice prepared by the
Utilities Division
15.
Letter from fire district regarding ownership and
maintenance of fire hydrants and certification of field
fire flow capacity testing
16. Copy of backflow prevention assembly test report
17.
Certification of the inflow/infiltration test for the
sewer lines by Engineer of Record
18. Copy of video tape test report
19.
Letter from Compliance Services section certifying that
the final inspection reveals that the Utility
facilities have been constructed in accordance with
County ordinances and regulations
if you have any questions, please call and advise accordingly.
attachments
doc:2094-2
~>
~t~
r--.I
m-<:
'0
0.. £r- ~.~
0'-C-q
t-O t-O ~1
Ltl ,Lq 0
,~, 0 10
0
0
0
0
C]
[Iq
rrl
ITl
I-4
Z
ITl
ITl
O"J
Z
n]
!
C,
0
m
Om
Z
Z
"no~
m-I
m
Z
,C, ,C, C,
II
II
II
11
il
II
II
Il
tl
11
11
II
Il
II
il
II
Il
II
II
II
II
II
II
11
II
tl
II
m
2613465 OR: 2657 PG: 0881
BILL OF SALE
THIS BILL OF SALE evidencing the sale and conveyance ofthe water and sewer utility facilities described
herein is made this 10Lb day of January ., ::111200.___9_0, by
CEDAR HAMMOCK COMMUNITY DEVELOPMENT DISTRICT
DISTRICT OFF1CES
210 N. UNIVERSITY DRIVE, SUITE 301
CORAL SPRINGS, FLORIDA 33071
(hereinafter referred to as "Seller"), to the BOARD OF COUNTY COMMISSIONERS OF COLLIER
COUNTY, FLORIDA, AS THE GOVERNING BODY OF COLLIER COUNTY AND AS EX-OFFICIO
THE GOVERNING BOARD OF THE COLLIER COUNTY WATER-SEWER DISTRICT, its successors
and assigns, (hereinafter referred to as "Buyer").
WITNESSETH:
The said Seller, for and in consideration of the sum of Ten Dollars ($10.00) and oth6r good and
valuable consideration to said Seller in hand paid by said Buyer, the receipt whereof is hereby acknowledged.
has granted, bargained, sold, transferred, set over and delivered, and by these presents does grant bargain,
sell, transfer, set over and deliver unto the Buyer, and Buyer's heirs, successors and assigns forever, all those
certain [identify type of utility facilities by inserting water, or sewer, or water and sewer] utility facilities
lying within the following described land, together with appurtenant easement rightg for the operation.
installation and maintenance of said facilities, situate, lying and being in Collier Count,./, Florida, to wit:
(See Exhibit "A" attached hereto and
incorporated by reference herein.)
OR: 2657 PG: 0882
.The Seller, for itself and its successors, hereby covenants to and with the Buyer and its successors
and assigns that it is the lawful owner of the said goods and chattels herein referred to as utility facilities;
that said goods and chattels are free from all liens and encumbrances; that it has good fight, title and
authority to sell same, and that it will warrant and defend the same against the lawful claims and demands
of all persons whomsoever. Seller and Buyer are used for singular or plural, as the context requires.
IN WITNESS WHEREOF, the Seller has caused these presents to be executed tEz date and year first
above written.
Witness t'~~ ~'~
STA~ OF FLO~DA
CO~ OF COLLIER
By:
Peter R. Comeau
Chairman - Board of Supervisors
The foregoing Bill of Sale was acknowledged before me by
~ ~:~.-D P't,.-tt~-t T ,0t~ ~~OP'-~ , on behalf of the corporation.
Personally known to me or produced identification. Type of identification produced:
WITNESS my hand and official seal this
__ day of x-~e~ Ix3 I..L,a-e-~t ,
('~y C~mmission Expires:
Prepared By:
BANKS ENGINEERING, INC.
2150 GOODLETTE ROAD, SUITE 701
NAPLES, FLORIDA 34102
*** OR: 2657 PG: 0883 ***
EXHIBIT "A"
All water and sewer utilities are located within the platted Right-
of-Way or CUE's as shown on the plat of Cedar Hammock (Plat
Book 32, Pages 91-108) as recorded in Collier County Public
Records.
IR~IHIRIIG H¥IH $IRVlC~$
RIX
'/.613466 OR: 2657 PG: 0884
HCOR~I~ in the OUICI~ HCO~D$ o[ C0ttlaR ¢0~R~L ~t
03/30/2000 at 09:33XN DWIG~ I. BROCK, C],IRR
WARRANTY DEED
DeC-.TO
15.00
.TO
THIS INDENTURE made this ~0~h day of Jammry
,~]920u0, between
CEDAR HAMMOCK COMMUNITY DEVELOPMENT DISTRICT
DISTRICT OFFICES
210 N. UNIVERSITY DRIVE, SUITE 301
CORAL SPRINGS, FLORIDA 33071
(hereinafter referred to as "Grantor"), to the BOARD OF COUNTY COMMISSIONERS OF COLLIER
COUNTY, FLORIDA, AS THE GOVERNING BODY OF COLLIER COUNTY AND AS EX-OFFiCIO
THE GOVERNING BOARD OF THE COLL1ER COUNTY WATER-SEWER DISTRICT, its successors
and assigns, (hereinafter referred to as "Grantee").
WITNESSETH:
The said Grantor, for and in consideration of the sum ofTen Dollars ($10.00) and other good and
valuable consideration to said Grantor in hand paid by said Grantee, the receipt whereof is hereby
acknowledged, has granted, bargained and sold to the said Grantee, and Grantee's heirs, successors and
assigns forever, all water and sewer utility facilities lying within the following described land, together with
appurtenant easement rights for the operation, installation and maintenance of said facilities, situate, lying
and being in Collier County, Florida, to wit:
(Sec Exhibit "A" attached hereto and
incorporated by reference herein.)
and said Grantor does hereby fully warrant the title to said utility facilities, and will defend the same against
the lawful claims of all persons whomsoever. For the purposes of this conveyance, the utility facilities
conveyed herein shall not be deemed to convey any of the lands described in Exhibit "A." Grantor'and
Grantee are used for singular or plural, as context requires.
TO HAVE AND TO HOLD the same unto the Grantee and its assigns, together with the
right to enter upon said land, excavate, and take materials for the purpose of constructing, operating, and
maintaining utility £acilities thereon. Grantor and Grantee are used for singular or plural, as the context
requires.
IN WITNESS WHEREOF, the Grantor has caused these presents to be executed the date and year
first above written.
STATE OF FLORIDA
COUNTY OF COLLIER
By:
Peter R. Comeau
Chairman - Board of Supervisors
The foregoing Warrant Deed was ackno, ledged before me by /[5~---'l~-~.- ~ .(,~l~ ,
'~-'~O~T '/~TF~C.T , CF ~ I P~A..qDI~,. on behalf of the corporation.
Personally known to me or produced identification. Type of identification produced:
o
WITNESS my hand and official seal this
ilf. T~'c'... .Y~t~ l!
!1%':,'?....?: ~: ~te, am I[ ..
IL,""".:::""'
(Affix Notary Seal)
Prepared By:
BANKS ENGINEERING, INC.
2150 GOODLETTE ROAD, SUITE 701
NAPLES, FLORIDA 34102
*** OR: 1657 PG: 0886 ***
EXHIBIT "A"
All water and sewer utilities are located within the platted Right-
of-Way or CUE's as shown on the plat of Cedar Hammock (Plat
Book 32, Pages 91-108) as recorded in Collier County Public
Records.
COLLIER COUNTY GOVERNMENT
COMMUNITY DEVELOPMENT AND ENVIRONMENTAL SERVICES DIVISION
ENGINEERING REVIEW SECTION
February. 3, 2000
Planning Services Department
2800 North Horseshoe Drive
Naples, Florida 34104
Tony Squitieri
Banks Engineering, Inc.
2150 Goodlette Rd. #701
Naples, FL 34102
Re: Cedar Hammock Clubhouse
Dear Tony:
This is to inform you that the above referenced project has been granted preliminary approval by
Engineering Review in compliance with Collier County Land Development Code, Section 3.
All water and/or sewer facilities approved, accepted and required to be maintained by Collier
County shall be conveyed to the County pursuant to the provisions set forth in Collier County
Ordinance No. 97-17, as amended.
You are reminded that it is your responsibility to petition the Development Services Director for
final approval of the improvements upon the expiration of the minimum one (1) year
maintenance period. After satisfactory completion of all final inspections., the Board of County
Commissioners shall grant final approval of the required improvements establishing County
responsibility for maintenance of the required improvements if it is the Board' s desire to accept
and maintain the facilities.
If you should have any questions or if we may be of assistance, please advise.
Very truly yours,
Shirley
NYX
Engineering Technician II
CC-'
Paul Mattausch, Water Director
Diane Deoss, Public Works
Phone (941) 403-2400 Fax (941) 643-6968 www. co.collier, fl.us
FIDELITY GUARANTY AND ACCEPTANCE CORP.
Box 2863, HOUSTON, TEXAS 77252-2863
(713) 599-2575
IRREVOCABLE STANDBY LETTER OF CREDIT NO. 00005
...... ,- - ~,'._ .~_~-,M'~ .:... - . ~ ..~=-~a ~.:: ,~ '_-:~;' ;-,4;~,.; - .-Z.-~K:-~.~L;[-~.~C~:' ~ L~;_~¥',~c3kJA~ANTYANDAGCEFrI-ANC~
DA~ OF ISS~: J~Y 14, 2~
PEA~ OF~Y: AT ISS~'S C~~
~ _.' _ . , .. ~ - . .
~' ' S~E~'~~'PE~~ ~
IS8~ ~ESS AT LE~T SI~ (~) DAYS P~OR TO
~RS~Y DA~; ~ ISS~R~'8
~T~G BY ~IS~D ~ ~T ~ ISS~R EL~ N~'~
A~~ TO ~ BUS--SS ~ ~ STA~ OF ~O~A
(~~R "~P~C~") 1~91 ~ ~ C~8 P~~,
FORT ~, ~ 33912
..... c~~;,'.. .... '.,:: $1~3~,16:~g~,~O ~'A~~ ~~
PA~ AG~ST ~~$ DET~
~CT;'~' sATIsFACTORY ~~AT~'P~o~CE SEC~TY
PRO~ED TO ~ FOLLY ACCEP~D BY ~ BE~FICI~Y."
U.S. HO~ CO~O~ON C~D~ NO. ~5 DAT~ I~Y 14, 2~." ~ O~G~
LET~R OF C~DIT ~N~ ~L ~~S, · ~, ~ST BE P~SEN~D FOR PROPE~ '
E~RSE~NT.
~S LE~R OF ~D~ SETS FOR~ ~ ~ ~ ~S OF ~ ISS~'S
~T~G ~ SUCH ~ERT~G ~L NOT ~ ~ WAY BE MOD~mD,
AG~E~ ~~CED TO ~ OR'~ ~ ~S LE~R OF C~IT ~LA~S,
~ ~ SUCH ~~CE S~IJ. NOTBE D~D TO ~CO~O~TE
~N~ ~ ~~, ~S~~ OR AG~E~.
~SSUER ~y ENGAGES WITH BENEFICIARY THAT D!~., T(S) DRAWN UNDER AND IN~
COM~'HA~CE wrrH TH~ T~,~S' OF 'THtS CAEmT' winL ~' t~OLY'~IONORED ~¥ ]S S~I~
PRESENTED WITHIN THE VALIDITY OF THI. S CREDIT.
..THIS Cg~._I]~_'IS_ S...LI~m..C~_ TO THE UNIFORM CUSTOMSAND P1LACTICE FOR ~~"~
:' ,C; S::~' '- ' '-
· - ~' ~ ' -~' '~'-~- C ~ ,.; ,%' ~ ~hC' ~.,,~;- '~'~L:~ ~R~~ ~ L bu. ~A?~ -" A;,.D A~GE: :NCE CC, R~: :U~.,T'F GUAR~ANDA~EPT~C~
~DA'.-- - A~[j AC~DTAN~- .]~.D~- ~ ~ ' ~%" ?..2 ',::'.L-~:~'.Z:': L'?R-~ :: ~2T. '~ GIJAKA,uTv AND ACC':: · '~C~ CFF. P - {}EL~TY GIJARA~ANDA~EPTANCE
- . a...-._ '-.~,, .? ..... :. -]~-;' - --: '~ -_ '_ -'- '- A",C :.:',F'~,~C:; '"';~.;:',' GUARAN~ AND ACCEPTANCE
Professional Engineers, Planners & Land Surveyors
January24,2000
Collier County Board of County Commissioners
Collier County Government Complex
3301 East Tamiami Trail
Naples, FL 34112
Reference:
CEDAR HAMMOCK - CLUBHOUSE - SDP 99-152
FINAL PAYMENT CONFIRMATION
Ladies and Gentlemen:
We do hereby certify that no outstanding money is owed to us for engineering fees at this time
associated with the design and certification of the water and gravity sewer systems at the above
project.
Sincerely,
BANKS ENGINEERING, INC.
David R. Underhill, Jr., P.E.
Florida Registered Engineer #47029
DRU/jmp
S:\Reception~Letter~\12xx\1263\County\Clubhouse\Clubhouse Utility Tumover\1263_FinalPaymentConf-Clubhouse.wpd
Lee County: 10501-104 Six Mile Cypress Parkway, Fort Myers, Florida 33912 · (941)939-5490. Fax (941)939-2523
Collier County: 2150-701 Goodlette Road, Naples, Florida 34102 (941)403-8866 Fax (941)403-8868
ngineerin!3,
Professional Engineers, Planners & Land Surveyors
January24,2000
Collier County Board of County Commissioners
Collier County Government Complex
3301 Tamiami Trail East
Naples, Florida 34112
Reference: CEDAR HAMMOCK - CLUBHOUSE - SDP 99-152
PRESSURE TESTING CERTIFICATION
Ladies and Gentlemen:
We witnessed pressure testing on the potable watermain and fire main on December 15, 1999, per the
standards set forth in the Collier County Utilities Ordinance.
The test results are as follows:
1. Potable Watermain;
Start: 9:00 a.m. ~ 155 psi
Finish: 11:00 a.m.~ 155 psi
No leakage was observed.
Total Length Tested = 195 Feet (8")
Allowable Leakage = N/A Gallons
Amount Required to
Re-establish Test Pressure = N/A Gallons
Fire Main;
Start: 9:00 a.m. ~ 205 psi
Finish: 11:00 a.m. ~ 205 psi
No leakage was observed.
Total Length Tested = 255 Feet (4")
Allowable Leakage = N/A Gallons
Amount Required to
Re-establish Test Pressure = N/A Gallons
We do hereby certify that the watermain and fire main have passed pressure testing as set forth by
Collier County Utilities Ordinance.
Sincerely,
BANKS ENGINEI~RING, INC.
David R. Underhill, Jr., P.E.
Florida Registered Engineer//47029
DRU/jmp
S \Reception~Lerters\l 2xx\1263\County\Clubhous¢\Clubhouse Utility Turnover\1263_PressureTesl-Clubhouse,wpd
Lee County: 10501-104 Six Mile Cypress Parkway, Fort Myers, Florida 33912 · (941)939-5490 · Fax (941)939-2523
Collier County: 2150-701 Goodlette Road, Naples, Florida 34102 ' (941)403-8866 · Fax (941)403-8868
Jeb Bush
Governor
Department of
Environmental Protection
South District
P.O. Box 2549
Fort Myers, Florida 33902-2549
David B. Struhs
Secretary
January 12, 2000
Peter R. Comeau, Regional Vice President
U.S. Home Corporation
10481 Six Mile Cypress Parkway
Fort Myers, Florida 33912
Re:
Collier County - PW
Cedar Hammock - Clubhouse
(Collier Countv Regional WTP)
163189-001 -DSGP
Southwest Coast EMA
Dear Mr. Comeau:
This acknowledges receipt of certification that the subject water distribution system extension has
been completed in accordance with the plans and related materials permitted by this agency under
Permit Number 163189-001-DSGP dated December 21, 1999.
Based on this certification and satisfactory bacteriological results, we are approving these .
facilities for service. Your continued cooperation in our xvater supply program is appreciated.
S~n~rely,
Charles R. Davault/-l'~*
Professional Enginee~
Water Facilities
CRD/MFJ/skxv
CC:
/David R. Underhill, P.E.
Thomas E. Kuck. P.E.
"More Protection, Less Process"
Pr/nted on recycled paper.
Florida Department of ,nvJronmGllta] Protection
DOMF~TIC WASTEWA'rER CO~._!_.FCTIONfTRANSMI~ON SYSTEMS
CERTIFICATION OF CO~ON OF CONSTRUCTION
INSTRUCTIONS: TI~ form is to be cc,~iAet~d and submitted so the ~z, prim' to plneini the sYmnn into operation. A
collection/imperils, ion sys~n should not be placed into operatio~ wid~ut prior Department approval. All ~,'~ is to be typed or
prinu~d in ink ami ail blanks must be filled.
Construction Permit No:' 5225g-074-DWC-~*L
Narn~ of Project Cedar H~vrmcl~ -
Name of Owne~: U.S. Home
Dated
Na~e of design engineer and Florida regisu~on ,~umber (if diffem~ from mgiaeer sia;ning cenif~ion):
Da~(s) connec~on to ~ti.~in~g sys~m or trram~t plaut:
Treaunent plant servi~ projoct
Nan,: South Cottony
DF.P ~n Number (also known as WAFR or GMS Identification
Subs2nthl dev~o:~ f~xn thc approvcd plans and Sl:~'ff. zcafions
WAIVER AND RELEASE OF LIEN
UPON FINAL PAYMENT
The undersigned lienor, in consideration of the final payment in the amount of
$ -0- , hereby waives and releases its lien and right to claim a lien
for labor, services or materials furnished to (customer) U.S. HOME ODRP. on the job
of (owner property) CEDPaR ~ , to the following described property:
CEDAR HAMMOCK CLUBHOUSE.
1-12 2000.
Dated On ,:l~
Mitchell & Stark
Const. Co., Inc.
kienor's Name
6001 Shirley St.
Address
Naples, FL 341 09
Brian Penner
P,'inted N:,me
NOTE: This is a statuto~, forfn prescribed by Section 713.20, Florida Statutes
(1996). Effective October 1, 1996, a person may not require a lienor to furnish a
waiveF or release of lien that is different from the statuto~, form.
COLLIER COUNTY GOVERNMENT
PUBLIC WORKS DIVISION
3301 E. TAMIAMI TRIAL
NAPLES, FLORIDA 34112
(941) 732-2575
FAX: (941) 732-2526
January07,2000
Mitchell and Stark
6001 Shirley Street
Naples, Florida 34109
Re: Bacteriological Analysis Results - Main Clearance
Attached please find the analytical results on the following water main clearance project:
Cedar Hammock Clubhouse. These results were found to be acceptable by Collier
County Laboratory, #55261.
Should you have any further questions regarding this matter, please contact me at (941 )
352-7004.
Sincerely,
,
Howard B. Br6gdon
Laboratory Supervisor
State of FLorida
Department of Health
Office of Laboratory Services
JacksonvilLe, #i~.i, PensacoLa
Tampa, West PaLm Beach
DRINKING WA TER
BACTERIOLOGICAL ANALYSIS
LAB USE ONLY
Press hard, (5) copies
· .~ .. ~. : £.:..;- _. ? ~."": *,~: :;,.
SYSTEM NAME:
ADDRESS:
COLLECTOR: ~":~ E!~ ~.',~j?d~v~. ~
SAMPLE S[TE (LocaLity or Subdivision):
DATE AND TIME COLLECTED: t~--~L ...... ~.i
TYPE OF SUPPLY(CircLe one): C(~C~oo~ni
ty water s~stem~
SYSTEM I.D. NO: SYSTEM PHONE #:
...... COIJNTY: DISTRICT: ....
COLLECTOR PHONE #:
- ~ ~:: ~!~:~"!: ,~fi~i:l' - ..... J':':-2,_ :_..ii.i
Noncommunity water system
Nontransient - noncoff~aunity water system
Private well Swimming pool BottLed water Limited Use system
TYPE OF SAMPLE(CircLe one): CompLiance Repeat Replacement ~Main clearanc~ WeLl survey Other
(Check Box)
P-]-Oistribution [ ] Check here if payment made
[ ] Raw to county public health unit
TO BE COMPLETED BY COLLECTOR OF SAMPLE TO_BE COMPLETED BY LAB
ANALYSIS METHOD: fMF~ MTF HMO-MUG PA
COLL. SAMPLE POINT C[ NON 'L~OI~FIRM CONFIRM
NO. (Specific Address) RES'D pH COLIFORM *TOTAL TOTAL FECAL E. COLI SAMPLE NUMBER
* ResuLts in this column are presun~otive. Total coliform and fecal :oliform or E. co[i confirmation wiLL foLLow in 24-48 hours.
p - Co[iforms are present C - ConfLuent growth TA - Turbid, Absence of gas or acid
A - Cotiforms are absent TNTC - Too numerous to count
INVOICE ADDRESS (if different than address beLou):
~:~'"':!'~::.~: !Ji~~ 'iim~i
INTERPRETATIONS-REMARKS BY. PROGRAM REVIEWER
NAME AND MAILING ADDRESS OF PERSON/FIRM TO RECEIVE REPORT
REVIEWING OFFICIAL:
TITLE:
( )
( ) SATISFACTORY
( ) INCC)MPLETE COLLECTION INFOR~LRTION
( ) REPEAT SAMPLES
( ) REPLACEMENT SAMPLES
State of FLorid.
Department of HeaLth
Office of Laboratory Services
JacksonviLLe, Miami, PensacoLa
Tampa, Weat PaLm Beach
DRINKING WA TER
BACTERIOLOGICAL ANALYSIS
-. ,."~=,~} :3%'~ LAB USE ONLY
TESTED
Da~e~ i ~-~-~ By:ROD
' CONFIRMED
SYSTEM NAME:
ADDRESS:
COLLECTOR:
SAMPLE SITE (LocaLity or Subdivision):
DATE AND TIME COLLECTED: i~--~--~9
TYPE OF SUPPLY(CircLe one):
Press hard, (5) copies
Coi Iier County Water Dept 5114069
SYSTEM I.D'. NO: SYSTEM PHONE #:
=30! *Tam;am; T'rai', Na~le5,
R. 0' DDNNELL. COLLECTOR PHONE #:
CEDAR .....
~.h .. .........CLUBHOUSE
TYPE OF SAMPLE(CircLe one):
~nit¥ water sys~ Nonco~nunity water system Nontransient - noncoamJnity Mater system
Privat6 ~et[ S~in~ning poD[ Bott[~ ~ate~ Limited Use syst~
C~[iance Re,at Reptac~nt ~n c[eara ~e[[ survey Other
(Check Box)
~ Distri~tion ~ [ ] Check here if ~nt ~de
[ ] Ra~ to county ~bLic health uni
TO BE COMPLETED BY COLLECTOR OF SAMPLE ~i~E COMPLETED BY LAB
ANALYSIS METHO0: (MFJ MTF MMO-MUG PA
COLL. SAMPLE POINT Ct NON CORTIRM CONFIRM
NO. (Specific Address) RES~O pH COLIFORM *TOTAL TOTAL FECAL E. COLI SAMPLE NUMBER
* ResuLts in :his coL~m are prestznptive. Total coliform and fecal coliform or E. coii confirmation uiLL foLLow in 24-48 hours.
p - CoLiforms are present C - ConfLuent growth TA - Turbid, Absence of gas or acid
A - CoLiform are absent TNTC - Too ncrnerous to count
INVOICE AOORESS (if different than address betoa): INTERPRETATIONS-REMARKS BY. PROGRAM REVIEWER
~MARKS: DAY TWO ,
NAME AND MAILING ADDRESS OF PERSON/FIRM TO RECEIVE REPORT
REVIEWING OFFICIAL:
TITLE:
SATISFACTORY
INCOMPLETE COLLECTION INFORMATION
REPEAT SAMPLES
REPLACEMENT SAMPLES
State of FLorida
Department of HeaLth
Office of Laboratory Services
Jacksonville, Miami, Per~acoLe
Tampa, gent PaLm Beach
DRINKING WA TER
BACTERIOLOGICAL ANALYSIS
TESTED
[CUNF I R~IEIJ
:::" .'. '? i ' ? > .
LAB USE ONLY
Press hard, (5) copies
-~: '_:- :~. .........
SYSTEM NAME: SYSTEM I.D. NO:
ADDRESS: ~'--~.E~.','q,! -;"~Z~ ~ :".:~:;?~ ~"--.; - COUNTY:
COLLECTOR: .... .:" :" '.... "
SAMPLE SITE (Locality or Subdivision):
SYSTEM PHONE #:
COLLECTOR PHONE #:
DATE AND TINE COLLECTED:
TYPE OF SUPPLY(Circle one): Noncemmunity ~ater system Nontransient - noncona~nity ~ater system
Pr~v~ ~in~ing pool Bottled ~ater~ited Use system
TYPE OF SAMPLE(Circle one): Compliance Repeat Replacement ~arance "gel[ survey Other
(Check Box)
[ ] Distribution [ ] Check here if payment made
[ ] Ra~ to county public health uni
TO BE COMPLETED BY COLLECTOR OF SAMPLE T~E COMPLETED BY LAB
ANALYSIS METHOD: /'-~'~"~ HTF HMO-MUG PA
COLL. SAMPLE POINT Cl NON ~COR~IRM CONFIRM
NO. (Specific Address) RES'D pH COLIFORM *TO~L TOTAL FECAL E. COLI SAMPLE HUMBER
~1 ,'.~-:,~,>~_ ~. ~. ~ ~!,~ ~.'~z~ ....~ ~:~' ..... i ' -~. , -
* Results in this column are presumptive. Total coliform and fecal coliform or E. coLi confirmation ~iLL fotLo~ in 2~-~8 hours.
p - Coliform are present C - Confluent growth TA - Turbid, Absence of gas or acid
A - CoLiforms are absent TNTC - Too numerous to count --
INVOICE ADDRESS (if different than address below): INTERPRETATIONS-REMARKS BY. PROGRAM REVIEgER
xe_°
HAME AND MAILING ADDRESS OF PERSON/FIRM TO RECEIVE REPORT
REVIEgING OFFICIAL:
TITLE:
SATISFACTORY
INCOMPLETE COLLECT[ON INFORMATION
REPEAT SAMPLES
REPLACEMENT SAMPLES
State of Florida
Depert~ent of Health
Office of Laboratory Services
decksonviLLe, Nimai, Pensacola
Tm, West Pe[m Beach
DRINKING WA TER
BACTERIOLOGICAL ANALYSIS
TESTED
CON~ I H~ED
SYSTEM NAME:
ADDRESS:
Press hard, (5) copies
· .. _: -: '; i~.: ...,.:*: ';: ;, ~ ..:-. ': c"' ': ~; "~ i:-' '~: ._~ i ~ ~+ I/-'.. ~.~ ~-~
SYSTEM I.D.. NO:
.. ~:'. -' :*?: ~' :. ~. ::' 7.. T':'?.Z .._~ ;",ia'~;'.:i~'--.~ !-_ COUNTY: L:oil!e~'~
SYSTEM PHONE #:
DISTRICT:
ii
COLLECTOR: ~1'""'" ," ' L"~ COLLECTOR PHONE #: .~,~ ~:.~-:.
SAMPLE SITE (Locality or Subdivision):
DATE AND TIME COLLECTED: /-..~ ~'~.0
TYPE OF SUPPLY(Circle one):ccon~numTy~ater ~st_y_~llL_-NonconmJnity ~ater system Nontransient - nonconmunity aater system
"l~t'i~[-l-"~-~uinming pool Battled uater Limited Use system
SAMPLE(Circle one): Compliance Repeat Replacement ~ainclearanc~'/ Well survey Other
TYPE
OF
(Check Box)
[ ] Distribution ? [ ] Check hqre if payment made
[ ] Ra~ to county public health unit
TO BE COMPLETED BY COLLECTOR OF SAMPLE TO_BE COMPLETEO BY LAB
ANALYSIS METNO0: t/'~lqF''', MTF MMO-MUG PA
COLL. SAMPLE POINT Cl NON 'L'~R~IRM CONFIRM
NO. (Specific Address) RES~O pH COLIFORM *TOTAL TOTAL FECAL E. COLZ SAMPLE NUMBER
I
* esutts in this col~am are pres~m~otive. Total coliform and fecal coliform or E. coil confirmation uill fotloe in 24-48 hours.
p - Coliform are present C - Confluent growth TA - Turbid, Absence of gas or acid
A - CoLiforms are absent TNTC - Too nLemrous to count
INVOICE ADDRESS (if different than address below):
'-'.:~ ~: ~-'..:: .L!*- *
INTERPRETATIONS-REMARKS BY. PROGRAM REVIEWER
eo
NAME AND MAILING ADDRESS OF PERSON/FIRM TO RECEIVE REPORT
REVIEWING OFFICIAL:
TITLE:
SATISFACTORY
INCOMPLETE COLLECTION INFORMATION
REPEAT SAMPLES
REPLACEMENT SAMPLES
MITCHELL & STARK CONSTRUCTION CO., INC.
LICENSED GENERAL CONTRACTOR
6001 SHIRLEY STREET
NAPLES, FLORIDA 34109-6202
PH: 941-597-2165
FAX: 941-566-7865
VERIFICATION OF FINAL COSTS
CEDAR HAMMOCK- CLUBHOUSE
DESCRIPTION
SANITARY SEWER SYSTEM
Sanitary Sewer Manhole 0-6
8" PVC Sanitary Sewer Main 0-6
Single Sewer Service
Cu[ In Sewer Service w/3co's complete
UNIT # UNIT TOTAL UP
EA I $1,575.00
LF 23O $14.73
EA 2 $503.00
LS 1 $1,675.00
SUB-TOTAL
TOTAL
$1,575.00
$3,387.90
$1,006.00
$1,675.00
$7,643.90
WATER SYSTEM
8" PVC DR 18 Water Main and Fi[tings
Fire Hydrant Assembly
Single Water Service
4" Gate Valve Complete
3" Gate Valve Complete
2" BFP (no meter)
Perm BlowOff
4" Fire Dectector System
4" P.I.V. & Siamese Connection
4" PVC DR 14 Fire Line
3" Sch 80 Water Main
LF 238 $12.53
EA 1 $2,084.00
EA 2 $945.00
EA 1 $538.00
EA I $394.00
EA I $1,050.00
EA 2 $918.00
LS 1 $9,138.00
EA I $2,375.00
LF 270 $12.25
LF 320 $5.35
SUB-TOTAL
TOTAL
$2,982.14
$2,084.00
$1,890.00
$538.oo
$394.00
$1,050.oo
$1,836.OO
$9,138.00
$2,375.00
$3,307.50
$1,712.00
$27,306.64
$34,950.54
AN EQUAL OPPORTUNITY EMPLOYER
Professional Engineers, Planners & Land Surveyors
January 24, 2000
Collier County Board of County Commissioners
Collier County Government Complex
3301 East Tamiami Trail
Naples, FL 34112
Reference:
CEDAR HAMMOCK - CLUBHOUSE - SDP 99-152
CERTIFICATION OF UTILITIES WITHIN PLATTED R.O.W. OR
DEDICATED EASEMENTS
Ladies and Gentlemen:
We do hereby certify that all water and sewer utilities to be dedicated to Collier County are located
within the platted Right-of-Way or CUE's as shown on the attached plat of Cedar Hammock (Plat
Book 32, gages 91 - 108), and within the proposed CUE being granted as part of the County
acceptance of this project.
Sincerely,
BANKS ENGINEERING, INC.
David R. Underhill, Jr., P.E.
Florida Registered Engineer #47029
DRU/jmp
S:~Reception\Letters~ 12xx\1263\County\Clubhouse\Clubhouse Utility Turnover\1263_ROWCcrt-Clubhouse wpd
Lee County: 10501-104 Six Mile Cypress Parkway, Fort Myers, Florida 33912. (941)939-5490 · Fax (941)939-2523
Collier County: 2150-701 Goodlette Road, Naples, Florida 34102 · (941)403-8866. Fax (941)403-8868
WARRANTY/GUARANTEE
THE UNDERSIGNED, Mitchell & Stark Construction Company, Inc. does hereby warrant
and/or guarantee the Watermain, Sanitary Sewer and appurtenances installed at CEDAR
HAMMOCK CLUBHOUSE, to be free from defects of materials and workmanship for a period
of at least one year from the date of acceptance by the Owner and Engineer.
THE UNDERSIGNED further agrees that it will, at its own expense, repair and replace all
materials or installations which violate the covenants herein contained.
DATE: 1-12-2000.
Mitchell & Stark Construction Company, Inc.
Michael J. I~qito, Project Manage
DATE: January 12, 2000.
State of Florida
County of Collier
Before me the undersigned notary public in and for the state and county aforesaid, personally
appeared MICHAEL J. DEVITO, PROJECT MANAGER of MITCHELL & STARK
CONSTRUCTION COMPANY, INC., a Florida Corporation, who acknowledged before me
that they executed the foregoing document.
Mo~(is Sons
NOTXRY PUBLIC
My commission · . .,?'~:,', ~:,;~,, Morris Sons
exp]res.:~?. ~,,
:,-- .t, (. ?,,': I,.'IYCOM,!~$$10N # CC67804~
· ,~ ,~ ~-',.'- ,' BONDED I~RU T;?OV FAIN INSURANCE. INC.
Official Receipt - Collier County Board of County Commissioners
CDPR1103 - Official Receipt
Trans N~_m_ber __ i Date
176389 ~ 01/24/2000 9:42:31 AM
Post Date ~ Pmt Slip # I Status
1__0!_(24_/2000'~ ~iiiiiiiiiii ~.~.6__~0_~ ~ POSTED
MITCHELL AND STARK
CEDAR HAMMOCK
Payor · MITCHELL AND STARK
Fee Information
i Fee~Co__d_e__i Description
i 42CYIN :COUNTY INVOICES
4080000001
Amount
$472.77
Total
$472.77
Waived
Payments
Payment Code i Account/Check Number
Total Cash
Total Non-Cash
Total Paid
Memo:
DOR#599
FULL BORE FLUSH/BACT. TEST
WO#11951/12131/19082
Amount:
$472.77'
$0.00
$472.77t
$472.77]
Cashier/location: GARRETT_S / 1
User: COLLAZO R
Collier County Board of County Commissioners
CD-Plus for Windows 95/NT
Printed:01/24/2000 9:42:58 AM
JA~-:~I-O0 OS:Se FR0~
ADC NO.
INVOICE
BOARD OF COUNTY COMMISSIONERS
COLLtEIP. COUN'~ COL~THOUSE COMPLEX
NAPLES, FLORIDA 34112
T-148 P.0i/01 F-$95
Invoice; No. DOR599
Date: OCTOBER 18, 1999
TO:
MITCHELL A ~ID STARK
602.7 SHIRL~ Y ST-
NAPLES, FL 33942
Apptic PO No.:
Department: Dept. of Revenue
Phone: 403- ~365
-DUE AND PAYABLE UPON RECEIPT
[BOARD DEPARTMENTS ONLY - CHARGES EXPENSED
UPON RECEIPT OF YELLOW COPY IN FINANCE]
CEDAR HAMM,: >CK
FULL BORE F~i~/BAcT- TEST
Work Order #119 H /12131/19082
Labor: 5.00
hrs- @ 15.00 per hour
EquiPment 5hrs. @ 12.00 per hour
Admins Cost
materials
lab anayls~s
gallons water us, ;d79,852
TOTAL- AMOUNT
75.00
60.00
26.97
0
270.00
40.80
$ 472.77
408/253212/3~.! 330/00000
MA," E CHECKS pAyABLE TO COLLIER COUNTY BOARD OF COLJNTY COMMISSIONERS
DETACH AND MAIL THI~ pORTION WITH YOUR CHECK TO
COLLIER COUNTY REVENUE SERVICES
2802 N. HORSESHOE DRIVE
NAPLES, FLOR1DA 34104
REVENUE ACCOUNT lnvo~:e: No. DOR599
FuND--~ COST CENT'I~ t OI~J/REV cOD~' I pROJE~CT[
4~8 000000 115100 o0000 Ami E. IlCi:
A/R No' 42CYIN
EXPENDITU__~ F. ACCOUNT
FUND t COST C~NTEII~
GOLDEN GATE FIRE CONTROL & RESCUE DISTRICT
4741 GOLDEN GATE PARKWAY · NAPLES, FLORIDA 34116-6901
(941) 455-2121 · FAX (941) 455-7917
January20,2000
Collier County Board of County Commissioners
Government Complex Center
3301 E. Tamiami Trail
Naples, Florida 34112
Dear Collier County Commissioners:
Subject: Cedar Hammock
The Golden Gate Fire Control & Rescue District does not accept ownership nor does it
maintain fire hydrants after their installation. Therefore, the Golden Gate Fire District
will not assume ownership or maintain the fire hydrants located within the Cedar
Hammock project.
Sincerely,
Donald R. Peterson
Fire Chief
DRP/pm
,~-, ~.~ ~.uoo zo~ o~ ~414557917 GOLDGATE FIRE ~=~TRT PAGE 02
GOLDEN GATE FIRE OONTROL & REVUE DISTRICT
4741 GOLDEN GATE PARKWAY · NAPt. F.~. FLORIDA 34116-6901
(941} 4~121 · FAX (941) 4,55-7917
.l'anuary 26, 2000
Tony Squiti~
Banks Ea~ineerin& Inc.
2150 Goodlette Road N.
Naples, Florida :14102
Sub}_'ect: Hvdrnnt Flow Te~_. - C_~ I'tnmmoc~
On ~anuary 25, 2000, tbe Golden Gate l/re Control & Rescue D/str/ct did a flow test on
one (1)fire hydrant/n the Cedar Hammock project. The remits are:
Hydrant 03502614 - C~,-' N__n~mock Blvd. & Tennis Court-
7~ Stalic PSI
72 Residual PSI
60 Pitot Flow PSI
4426 GPM at 20 PSI Residual
Before completion of the projeot, the hydrants need to be painted OSHA sa/cry yellow.
The caps need to be painted OSHA safety light blue. Also, blue road rdleaors need to be
installed to show location of all hydrants.
This Fu~ District does not accept ownership nor does it maintain £,~= hydrants alter their
installafio~
Total due the Golden Gate Fire Control District for thc flow test is S35.00.
Siacerel~,
Fire Chief
DRP/pm
Enclosure
v~ ~.~ ~vv l~: ~ ~414557917 GOLI)GATE FIRE DEPTRT PAGE 03
HydrM~ Flow Telt~
Hydrant N~mb~ e4~J m "~14'
01/25/2000
14 ..... _C.._o_..W.,_.Sco~_[,~R/F~.._NG INE ER
,Subtotal Te~t~:
8tltlc Reeid Pltot
78 72 60
CEDAR HAMMOCK BLVD & TENNIS COURTS
Pitm 2 GPM
0 1300
~0
5194
Max: 1300 442~ 4623 5104
MIn: 1300 4426 4823 6194
Avg: 1300 4426 4823 6194
Tolzl Flow T#t~: I
01/25/2000 16:19 Page'. I
Professional Engineers, Planners & Land Surveyors
Sanuary 24, 2000
Collier County Board of County Commissioners
Collier County Government Complex
3301 East Tamiami Trail
Naples, FL 34112
Reference:
CEDAR HAMMOCK- CLUBHOUSE - SDP 99-152
CERTIFICATION OF FIELD FIRE FLOW CAPACITY
Ladies and Gentlemen:
Based on the attached fire flow test we do hereby certify that the field fire flow capacity was
examined and meets the design criteria for the previously submitted water system calculations for
-the above referenced project.
Sincerely,
BANKS ENGINEERING, INC.
David R. Underhill, Jr., P.E.
Florida Registered Engineer g47029
DRU/jmp
S:~=c¢~ioa~H2a~,12J~'~aumy~Clubhmm~.~2lubhou~ Uglity Tumov~1263._Fi~FIcrwC~t-~21al~om~wpd
Lee County: 10501-104 Six Mile Cypress Parkway, Fort Myers, Florida 33912. (941)939-5490. Fax (941)939-2523
Collier County: 2150-701 Goodlette Road, Naples, Florida 34102 · (941)403-8866. Fax (941)403-8868
JAN-20--00 P.02
Customer Cedar
IF~ :49 AM TANN;4SSEE FIRE PROTECT. 941 405 9~35~5
COLLIER ~,,,OUNTY CROSS CONNECTIOf* --,ONTROL
Test And Maintenance Report
Hammock
SucctAddt'ess Cedar Hammock Blvd.
Location of Assembly C1 ubhouse
MaJlJng Address
Typc Of Asscmbly RP [ ]
Manufactt, rcr ~4 i 1 k i n s
Test Guagc Manufacturcr .......... M i dwe s t
Mctcr No. 990/40905
DC [~] PVB [ ] Fire Line ~ I Potable [ ]
Model 950DA Serial No. D06352
Gauge Serial No. I t~l 7 5 7
Date Tested 1 / I B/O0
Size
1'1
CHECK VALVE #1 RELIEF VALVE CHECK VALVE #2 PRES. VACUUM BREAKER
il i leaked opened at: _PSI [ ] leaked air inlet opened at laS]
[x] closed tight [x] closed fight did not open [ ]
gauge pre,sm e ' did not opcn [ ] gauge presaure check valve;
across check across check leaked [ ]
valve 14.2 PS! valve 1.5 . PSI held at.~ ........ PSI
[ vi clcaned only [ ] cleaned only [ ] cleaned only [ ) cleaned only
replaced: replaced: rcplaccd: replaced':
CV assembly [ i RV assembly [ ] CV assembly [ ] ~..V assembly
or or or disc, air in [ ]
disc [ } disc [ ] disc [ 1 disc, C\r { 1
o-rings [ I dinphragrn(s) [] o-rings [ ] si)ring, air [ ]
spring 11 spri,~g [] spring [] retainer J ]
stem/guide [ ] gt, ide [] stcm/guide [ ] guide [ ]
retainer [] o-rings [] retainer f] o-ring [ ]
lock hms [ I other [ ] lock nuts [ ] other I ]
or!mr Il other []
gauge lWC'.m'arc relief valve gauge pressure air inlet .... PSI
across check o[)cncd at :<ross check
Note: All ,'cp:fi~s shat! bc completed witlfin tcn (10) days.
I%,narks. Pa_s.%ee .....
I kcrcbv ccrut\' lb:it this data i~ accuratc and reflects thc proper opcration and maintcnancc of the assembly. ...... -
'l'tstc~. Kenneth R.
T, nnasse* Cert. No. H01053 Date t/18/00
Time
COLLIER (;OUNTY CROSS CONNECTION ~;ONTROL
'rest And Maintenance Report
Customer Cedar Hammock
Street Address Cedar Hammock B1 vd. Mailing Address
Location of Assembly C I ubhQu~O ..-
Type Of Assembly RP [ ] DC Ix] PVB [ ] Fire Line [ ~
Model ~50xL
__ ___ Gauge Serial No.
Date Tested
btanufacturer Wi i kl ns
Test Guagc Manufacturer Midwest
Meter No.
Potable [ }
Serial No. _9_p9368
141757
Sizc 3/4"
~/18/oo
CHECK VALVE #1 RE. LIEF VALVE CHECK VALVE #2 PRES. VACUUM BREAKER
[ ] leaked opened at: PS1 [ ] leaked air inlet opened at __PSI
[~] closed fight [ ~] closed tight did not open [ ]
gauge pressure did not open [ ] gauge pressure check valve:
across check across check leaked [ ]
valve 1.6 PSI vane 1.9 PSi held at .......... PSI
[ ] cleaned only [ ]clcancd only [ ] cleaned only [ } cleaned only
replaced: rep!aced: replaced: replaced:
rubber ldt [ ] ruhl)cr kit [ ] rubl,cr kit [ ] rubbcr kit 1' ]
CV assembly [ ] RV assembly [ ] {/iV assembly [ ] CV assembly ] ]
or or or disc, air m { ]
disc [ ] disc [ ] disc [ } disc, CV ] ]
o-rings [] ,liaphrag, n(s) [1 o-dngs [1 spE.~g, :,ir ] ]
scat l1 ,x.~t it .~c,~t 11 sp~:ipg, ¢:v J]
spring J ] :;pring J ] .~pring [ ] rctmncr J ]
stem/grade J ] guide J ] stem/~Hde [ ] gui.de j]
retainer Il o-rings 11 retainer [] o-nng [I
lock nuts J J ,)ti,er [ ] lock nuts [ ] other J ]
mhcr l1 other ['l
~auge lWCSsm'e relief vane ga,ge pressure air inl,.:t ....... PSI
:across check OlXmCd at ~:cross chec'<
valve .... PSI ........ PSI valve __PSI chk. valve ............ PSI
Nnte: All repairs shnll be completed within ten (I0) days.
Remarks_
I hereby certify that this data is accurate and reflects thc proper operation and maintenance of the assembly. - ....
Tester Kenneth R. Tannassee
H01053 1/18/00
Ccrt, No ............. Date .............
5:00 om
'I 'i in c
;Zn$inrerin$, i
Professional Engineers, Planners & Land Surveyors
January 24, 2000
Collier County Board of County Commissioners
Collier County Government Complex
3301 East Tamiami Trail
Naples, FL 34112
Reference:
CEDAR HAMMOCK- CLUBHOUSE - SDP 99-152
INFILTRATION TEST CERTIFICATION
Ladies and Gentlemen:
We do hereby certify that the collection system was examined and that no infiltration into the
collection system was noted for the above project.
Sincerely,
BANKS ENGINEERING, INC.
David R. Underhill, Jr., P.E.
Florida Registered Engineer #47029
DRU/jmp
S \Reception\Letters~ 12xx\ 1263\County\Clubhouse\Clubhouse Utilil3' Turnover\ 1263_InfillrationCert-C1 ubhouse wpd
Lee County: 10501-104 Six Mile Cypress Parkway, Fort Myers, Florida 33912. (941)939-5490 · Fax (941)939-2523
Collier County: 2150-701 Goodlette Road, Naples, Florida 34102 · (941)403-8866 · Fax (941)403-8868
~ TSe Finest in
Wasrewater Structure Rettabd~tarion. ~
C~-~O0, ~,m aecepeibte Idtumbous or el)oW
44~111aHo~.k liridl~t. I'lrk~vat. Nih I;f
..) CXI I £t_~ t~Jt~J
b".
~LXZIt ~0~ I~X'ZX, ZTX_~-
DATE OF REVIEW: 10-14-99
PROJECT NAME:
Cedar Hammock, Phase 1, and Clubhouse, Multi-Family Tract F-5 (South)
ENGINEER OF RECORD:
CONSTRUCTION COld'tRacTOR:
VIDEO CONTRACTOR:
Sewer Viewer
COMI(ENTS: Lines and services acceptable at this time but will review joint
at 125 {t. in one year to make sure Joint does not leak [n line
~ S37 to ~ #33
RECOMMENDATIONS:
xx__ I ACCEPTABLE:
~ R~VIEW NUMBERED COMMENTS IN ONE YEAR:
Nm~ERED CO~S UNACCEPTABLE:
OTHER RECOMMENDATIONS:
COLLIER COUNTY GOVERNMENT
COMMUNITY DEVELOPMENT AND ENVIRONMENTAL SERVICES DIVISION
PLANNING SERVICES DEPARTMENT
ENGINEERING REVIEW SECTION
Planning Services Department
2800 North Horseshoe Drive
Naples, Florida 34104
January 12. 2000
Mr. Tony Squitieri
Banks Engineering, Inc
2150 Goodlette Rd., N.
Suite 701
Naples, Florida 34102
RE: Cedar Hammock Clubhouse, Water & Sewer
Dear Mr. Squitieri:
A preliminary inspection of the referenced project was conducted by Randy Casey of the
Engineering Review Section of the Planning Services Department on January 12, 2000.
Conditions were found to be acceptable, and appear to meet County standards.
If you should have any questions, please do not hesitate to call Randy Casey at (941) 403-2418.
Sincerely,
En~~e°ebles~''
ring Inspections Supervisor
DN/taa/f:\Inspection form
Cedar Hammock Clubhouse, water & sewer
cc'.
Cindy Erb, Engineering Technician, Public Works
Joe Cheatham, Wastewater Director, Utilities
Paul Mattausch, Water Director, Utilities
Evelyn Ferguson, D.O.R. Billing Supervisor
Randy Casey, Engineering Inspector, Engineering Review Section
7Shirley Nix, Engineering Tech. II, Engineering Review Section
File